OPERATION
GENERATOR LOCATION
Read and understand all safety information before
starting the generator.
NEVER operate the generator inside any building, including
garages, basements, crawlspaces, sheds, enclosure, or
compartment, including the generator compartment of a
recreational vehicle.
Electrocution hazard. Never use the generator in a
location that is wet or damp. Never expose the generator
to rain, snow, water spray, or standing water while in
use. Protect the generator from all hazardous weather
conditions. Moisture or ice can cause a short circuit
or other malfunction in the electrical circuit. Using a
generator or electrical appliance in wet conditions, such
as rain or snow, or near a pool or sprinkler system,
or when hands are wet, could result in electrocution
Fire hazard. Only operate the generator on a solid, level
surface. Operating the generator on a surface with loose
material such as sand or grass clippings can cause debris to
be ingested by the generator that could block the cooling
vents or the air intake system. Allow the generator to
cool for 30 minutes before transport or storage.
The generator should be on a flat, level surface at all
times (even while not in operation). The generator must
have at least 5 ft. (1.5 m) of clearance from all
combustible material.
Do not operate the generator in the back of a SUV,
camper, trailer, truck bed (regular, flat, or otherwise),
under stairs, next to walls or buildings, or in any other
location that will not allow for adequate cooling of the
generator and/or the muffler. DO NOT contain generators
during operation.
14 |
Asphyxiation hazard. Put the generator in a well-
ventilated area. DO NOT put the generator near vents
or intakes where exhaust fumes could be drawn
into occupied or confined spaces. Carefully consider
wind and air currents when positioning the generator.
GROUNDING
Shock hazard. Failure to properly ground the generator
can result in electric shock.
Only use grounded 3-prong extension cords, tools, and
appliances, or double-insulated tools and appliances.
The generator neutral is bonded to the frame. There is a
permanent conductor between the generator (stator wire)
and the frame. If this generator will be used only with cord
and plug equipment connected to the receptacles mounted
on the generator, National Electric Code does not require
that the unit be grounded. However, other methods of
using the generator may require grounding to reduce the
risk of shock or electrocution.
Before using the ground terminal, consult a qualified
electrician, electrical inspector, or local agency having
jurisdiction for local codes or ordinances that apply to the
intended use of the generator.
DISCONNECTING THE BONDED NEUTRAL
Removing the bonded neutral disables the GFCI protection
from the 5-20R receptacles. The bonded neutral should
only be removed under specific circumstances. Consult a
qualified electrician to determine if the situation requires
disconnecting the bonded neutral.
1. Remove the alternator cover.
2. See Figure 1. Remove the bonded jumper wire and reinstall
the nut.
1
NOTICE