Jumper 8
Room air control selection:
Jumper 8 bridged.
Jumper 9
Switch-off function:
Jumper 9 bridged
Switch-off function blocked.
The ventilation unit can no
longer be switched off at
the room air control.
Factory setting
Jumper 10
Jumper 10 open.
Alternative
Jumper 10 bridged,
CO
-, VOC- or RFS-
2
sensor activated.
Without a sensor, jumper
10 must be open.
9.6.4 Frost protection temperatures
An internal frost protection monitoring
prevents the heat exchanger from freezing up
at low external temperatures. A temperature
sensor monitors the temperature at the heat
exchanger permanently.
If the outgoing air temperature drops below
the predefined frost protection switch-off
value T-Off, the supply air fan switches off
until the temperature has risen to the defined
frost protection switch-on value T-On.
We recommend the deployment of
i
an electrical outside air preheating
register, in order to ensure the frost-
protection function in passive-energy
houses. This avoids cycling the
outside air fan.
On/off switching points, adjustable with
jumpers J4 and J5
J4
J5
0
0
0
1
1
0
1
1
0 = Jumper open
1 = Jumper bridged
T-Off
T-On
0 °C
7 °C
0 °C
10 °C
2 °C
9 °C
2 °C
12 °C