Fault: Fans do not operate.
Fault message:
All 3 LEDs at the RB-ZF4 flash. The fault
message appears immediately and goes
out after approx. 1 minute.
Cause
Frost protection
temperature sensor
failed (not connec-
ted, cable break or
short-circuit).
Fault: Fans do not operate.
No fault message:
All LEDs at the RB-ZF4 are switched off.
Cause
Differential
pressure controller
has triggered.
Front shutter
opened.
Device powered-
off.
Rectification
 Check
connection.
 Check frost
protection
temperature
sensor.
Exchange it if
necessary.
Rectification
 Check the differ-
rential pressure
controller.
Determine the
reason why it
triggered. If
necessary,
exchange the
differential
pressure
controller.
 Check fuse.
 Check front
cover.
8. Installation preparations
8.1 Transport
The ventilation unit is delivered on a palette.
● Adhere to the valid safety and accident
prevention regulations for transportation.
● The permitted maximum load for lifting
gear, chains, ropes, etc. must be sufficient
for the total weight of the ventilation unit.
● Nobody should ever stand under a
suspended load.
8.2 Requirements at the installation
site
● Room with an ambient temperature from
+ 10...+ 40 °C, e.g. in the cellar or in the
loft.
● Level, hard installation surface. This is
important in order to avoid vibration-based
noises.
● Siphon for condensation run-off. Sufficient
incline for the condensation drain.
Condensation drain with drain tap.
● Working room for operative and mainte-
nance work: at least 70 cm in front of the
unit.