Maintenance
ER Code
Alarm
25
Datalogger
26
Conductivity measurement
27
Conductivity exceeded
29
Communication
30
I/O module fault
31
EEPROM defective
32
Under voltage
33
Adjustment parameter
34
Main board communication
faulty
35
Digital limit switch voltage
faulty
36
Analogue limit switch
voltage faulty
37
Limit switch voltage MBV1
39
Pressure jumper
40
Level jumper
41
Replace battery
42
Bus module
43
Outside operating range
11
Maintenance
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wear protective gloves.
•
Please place appropriate warning signs in the vicinity of the device.
CAUTION
Risk of injury due to pressurised liquid
If installation, removal or maintenance work is not carried out correctly, there
is a risk of burns and other injuries at the connection points, if pressurised
hot water or hot steam suddenly escapes.
•
Ensure proper installation, removal or maintenance work.
•
Ensure that the system is de-pressurised before performing installation,
removal or maintenance work at the connection points.
The 'Servitec' must be serviced annually or after 16,000 degassing intervals,
whichever comes first.
Note!
Shorter maintenance intervals are required if the default setting for
interval degassing of 8 degassing cycles and 12 h idling time exceeds
the following times for continuous degassing.
•
Continuous degassing time of about 14 days
Or
•
Continuous degassing time of 7 days + 1 year interval degassing
with default setting
50 — English
Causes
•
No SD card inserted
•
The SD card is write-protected
•
The SD card has not been recognised
Measured value outside the measuring range. •
•
Set value exceeded.
•
Cartridge capacity expired.
Master-slave communication or master
controller faulty
•
I/O module defective.
•
Connection between option card and
controller faulty.
•
Option card defective.
•
I/O module activated but not present.
•
EEPROM defective.
•
Internal calculation error.
Supply voltage not achieved.
EEPROM parameter memory defective.
•
Connection cable between display and
I/O circuit board defective.
•
Main board defective.
Short-circuit of limit switch voltage.
Short-circuit of limit switch voltage.
Short-circuit of limit switch voltage.
Main board jumper does not match
configuration.
Main board jumper does not match
configuration.
Battery discharged.
Bus module was not detected.
Operating range exceeded.
Vacuum spray degassing — 01.04.2022-Rev. D
Remedy
•
Insert a FAT16 or FAT32-formatted SD card.
•
Disable write-protection.
Check set value in the customer or service menu.
•
Check the sensor and cabling.
•
Check set value in the Customer or Service
menu.
•
Replace the cartridge.
Check connection.
•
Replace the I/O module.
•
Check the connection between option card and
controller.
•
Replace the option card.
Inform Reflex Customer Service.
Check voltage supply.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Check the wiring at the digital inputs (water meter, for
example).
Check the wiring at the analogue inputs
(pressure/conductivity).
Check the wiring at the 2-way motorized ball valve.
Check jumper (J1) position.
Check jumper (J1) position.
Replace backup battery in control unit.
•
Check the set values.
•
Check the bus module.
•
Lower the system pressure.
•
Check ball valves on pump discharge side.
The maintenance intervals depend on the operating conditions and the
degassing times.
Do not exceed the maintenance intervals.
Perform servicing, if the intervals have been exceeded.
Note!
Maintenance/service work must be carried out and acknowledged by
specialist personnel or the Reflex Customer Service.
Note!
The annual maintenance is displayed upon expiry of the set operating
time. •
Press "OK" to acknowledge the "Service recommended"
message.
The maintenance schedule is a summary of maintenance tasks to be carried out
regularly.
Maintenance task
▲ = Check, ■ = Service, ● =
Clean
Check for leaks, 11.1 "Exterior
leak test", 51.
•
"PU" pump
•
Screw connections
•
"DV" degassing valve
Vacuum function test.
–
8.5 "Vacuum test", 43
Alarm reset
–
–
"OK"
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Conditions
Interval
▲
■
Annually
▲
Annually