4.
Set the system-specific values for the individual areas.
Use the "Left" and "Right" buttons to select the display value.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".
Press "i" to display a help text for the selected area.
Press "X" to cancel your input without saving the new settings. The
controller automatically opens again the list.
10.1.2 Service menu
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service. A partial summary of the settings stored in the Service menu
is proved in the Chapter Default settings.
 10.1.3 "Default settings",  47
10.1.3 Default settings
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Language
EN
Time
Date
Servitec
Magcontrol
Minimum operating
1.5 bar
pressure p0
Safety valve, pressure
3.0 bar
Degassing
Degassing programme
Continuous
degassing
Continuous degassing
24 hours
time
Make-up
Maximum make-up
0 Litres
quantity
Maximum make-up time
20 minutes
Maximum make-up cycles 3 cycles within
2 hours
Softening (only if "Water treatment with Softening")
Shut off make-up
No
Hardness reduction
8°dH
Soft water capacity
0 Litres
Cartridge replacement
18 months
Desalination (only if "Water treatment" with Desalination")
Conductivity monitoring
No
Shut off make-up
No
Hardness reduction
8°dH
Soft water capacity
0 Litres
Cartridge replacement
18 months
Remarks
Display language
For systems with diaphragm-
type expansion vessel
Only Magcontrol
Actuating pressure of the
system's heat generator safety
valve
Only if controller with "With
water meter yes"
Magcontrol and Levelcontrol
Magcontrol and Levelcontrol
In the case of soft water
residual capacity = 0
= Target – Actual
Attainable water capacity
Replace cartridge
In the case of soft water
residual capacity = 0
= Target – Actual
Attainable water capacity
Replace cartridge
Vacuum spray degassing — 01.04.2022-Rev. D
Parameter
Setting
Next maintenance
12 months
Volt-free contact
YES
Service menu
Parameter
Setting
Make-up
Pressure differential,
0.1 bar
"NSP" make-up
Pressure differential,
0.2 bar
filling pressure PF – P
0
Maximum filling duration
10 h
Degassing
Idling times between
10 hours
degassing intervals
Number of degassing
n = 8
cycles for each interval
Daily start
08:00 h
10.1.4 Degassing programmes – overview
You can choose between 3 degassing programs:
Continuous degassing
Usage:
For device commissioning.
For degassing of the water after a device or facility system repair.
Activation:
An automatic activation occurs after completion of the start routine
during initial commissioning.
Times:
The time can be set in the Customer menu.
The default setting is 24 hours. Subsequently, the system
automatically switches to Interval degassing.
In continuous degassing, the degassing cycles are sequentially performed for 24
hours.
Interval degassing
Usage:
For continuous operation of the device.
Activation:
Automatic activation occurs after the ending of continuous
degassing.
Times:
8 degassing cycles per interval is set in the Service menu.
After 8 intervals there is an idling time of 12 hours.
The times for interval degassing are stored in the Service menu.
The daily start of interval degassing is at 8:00 a.m.
Interval degassing is preset in the customer menu as the default setting.
Make-up degassing
Usage:
For gas-rich water from the make-up.
For summer operation when the circulating pumps of the facility
system are shut down,  9.1.4 "Summer operation",  45.
If the facility system water is not to be degassed.
Activation:
Automatic activation occurs at every water make-up.
During continuous degassing.
During interval degassing.
Times:
The make-up water is degassed for as long as it is supplied,
 10.1.1 "Customer menu",  46.
Controller
Remarks
Time left to the next due
maintenance
Only the messages marked in
the "Messages" list
Remarks
Only Magcontrol
Only Magcontrol
Only Magcontrol
Idling times between the
degassing intervals
Number of degassing cycles in
one interval
Start of the daily degassing
intervals
English — 47