ER Code
Alarm
01
Minimum pressure
02.1
Low water
02.2
Low water
04.1
Pump
06
Make-up time
07
Make-up cycles
08
Pressure measurement
10
Maximum pressure
11
Make-up quantity
12
Filling time
13
Filling volume
14
Discharge time
15
Make-up valve
16
Power failure
18
Parameter
Stop ˃ 4 hours
19
20
Maximum make-up quantity Set value exceeded.
21
Maintenance recommended Set value exceeded.
22
Blow-off time
24
Water treatment
Causes
For "Magcontrol" setting only.
Set value not reached
Water loss in the system.
Pump fault.
Expansion vessel defective.
Dry run protection: Low water switch
Defective.
Not cabled.
Triggered for too long.
Low water switch has actuated too often.
Pump disabled.
Pump jammed.
Pump motor defective.
Fuse defective.
Set value exceeded.
Water loss in the system.
Make-up line not connected.
Make-up output insufficient.
Continuous water loss in the system.
Controller receives incorrect signal.
For "Magcontrol" setting only.
Set value exceeded.
"With water meter" must be activated in the
Customer menu.
Set value exceeded.
Severe water loss in the system.
Set value for the maximum filling duration has
been exceeded.
Set value exceeded
Set value exceeded.
"DC" degassing line closed.
Dirt trap clogged.
Contact water meter measures without make-
up request.
No voltage supply available.
Setting parameter not entered correctly.
Longer than 4 hours in stop mode.
Blow-off time outside the set value. (Only if
appropriate sensors are used.)
Water capacity set value exceeded.
Time interval for replacement of the
cartridge exceeded.
Vacuum spray degassing — 01.04.2022-Rev. D
The system displays the possible causes for the fault.
3.
When the fault is eliminated, confirm the fault with "OK".
Remedy
Check set value in the customer or service menu.
Check water level.
Check pump.
Check expansion vessel.
Check low water switch.
Open the degassing line.
Clean the dirt trap.
Replace the degassing valve.
Clean the dirt trap.
Replace the degassing valve.
Rotate the pump with screwdriver.
Electrically test the pump motor
Replace the 10 A fuse.
Check set value in the customer or service menu.
Check water level.
Connect make-up line.
Check set value in the customer or service menu.
Seal the leakage in the system.
Check/connect the plug connection at the
pressure transmitter.
Check the cable for damage.
Check the pressure sensor.
Check set value in the customer or service menu.
Set the actuating pressure of the safety valve.
Check set value in the customer or service menu.
Check the water loss and correct, if necessary.
Check set value in the customer or service menu.
Check the water loss and correct, if necessary.
Check set value "Max. Fill Contact (128)" in the
service menu.
Check the water loss and correct, if necessary.
Check set value in the customer or service menu.
Open the degassing line.
Clean the dirt trap.
Check the 2-way motor ball valve (WV) for leak
tightness.
Connect to voltage supply.
Check setting parameter and correct if necessary.
Set the controller to Automatic mode.
Reset the "Make-up quantity" meter in the Customer
menu.
Carry out maintenance.
Check set value in the Customer or Service menu.
Replace water treatment cartridge.
Confirm cartridge replacement in the customer
menu by pressing the "OK" button twice in the
"Make-up" menu → "Soft water capacity (032)"
Controller
Alarm reset
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
English — 49