Installation
6.1
Installation conditions
6.1.1
Incoming inspection
The device is carefully inspected and packed prior to shipping. Damages during
transport cannot be excluded.
Proceed as follows:
1.
Upon receipt of the goods, check the shipment for
completeness and
possible transport damage.
2.
Document any damage.
3.
Contact the forwarding agent to register your complaint.
6.2
Preparatory work
Condition of the delivered device:
Check all screw fittings and electrical connections of the Servitec for proper
seating.
Tighten the screws and fittings as necessary.
Preparing the device installation:
Frost-free, well-ventilated room.
Ambient temperature > 0 to maximal 45 °C.
Level, stable flooring with a drainage facility.
Filling connection DN 15 to DIN 1988 -100/ -600 / DIN EN 1717.
Electric connection 230 V~, 50/60 Hz, 16 A with upstream ELCB: Tripping
current 0.03 A.
The Servitec can be operated in two different modes for water make-up. When
installing the Servitec, note its position within the system:
Pressure-dependent make-up of system water (Magcontrol).
Install the Servitec in the vicinity of the expansion vessel.
Level-dependent make-up of system water (Levelcontrol).
Install the Servitec on the system side in the return upstream of the
return flow admixture.

Note!
Servitec make-up line.
Use the Fillset system separator if the make-up line of the drinking
water mains is closed.
The applicable guidelines and regulations of the country of
installation must be observed.

Note!
Comply with the Reflex planning directive.
During planning, take into account that the working range of the
Servitec must be between the "pa" supply pressure and the "pe"
final pressure in the working range of the pressure maintenance
system.
6.3
Execution
ATTENTION
Damage due to improper installation
Additional device stresses may arise due to the connection of pipes or
system equipment.
Ensure that pipes are connected (torque-free) from the device to the
system without them being stressed or strained.
If necessary, provide support structures for the pipes or equipment.
ATTENTION
Property damage caused by leaks
Leaks in the connection pipes to the device can cause material damage to the
facility system.
• Use only connection pipes with appropriate resistance against the facility
system temperature.
In heating systems, preferably install the device in the return side.
In this manner, you ensure that the device is operated within the
permissible pressure and temperature ranges.
In systems with return admixtures or hydraulic switching points, the device
must be installed upstream of the admixture point to ensure degassing in
the "V" main flow volume at temperatures ≤ 90 °C.
36 — English
The device is pre-wired and must be adapted for the local system conditions.
Complete the water-side connection to the system and the electric connection as
shown in the terminal diagram,  6.5 "Electrical connection",  38.

6.3.1
Install the "DV" degassing valve (2) with the check valve (1) on the "VT" vacuum
spray tube. Check all screw fittings of the Servitec for proper seating.
6.3.2
The Servitec is installed on the floor. Select the attachment means according to
the floor properties and the weight of the Servitec.

6.3.3
6.3.3.1 Degassing line to the system
The device requires two "DC" degassing lines to the system. One degassing line
is intended for gas-rich water from the system, and the other one serves to return
the degassed water to the system. Shut-off devices for both degassing lines
have been pre-installed at the device. The connections of the degassing lines
must be made within the main flow volume of the facility system.
Vacuum spray degassing — 01.04.2022-Rev. D
Note!
During installation, pay attention to the operability of the valves and the
inlet options for the connecting lines.
Fitting the add-on components
Installation location
Note!
Consider a potential difference in head "h
vessel and the device when calculating the "P
pressure.
Hydraulic connection
" between the expansion
st
" minimum operating
0

Publicité

loading