Reflex Servitec 35 Mode D'emploi Original page 42

Masquer les pouces Voir aussi pour Servitec 35:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 54
Controller
5.
Touch the displayed crosses on the touch screen after each other.
6.
Switch the device off and on again at the main switch.
The touch screen is fully calibrated.
8.3
Modifying the controller's start routine
The start routine is used to set the parameters for device commissioning. It
commences with the first switching on of the controller and can only be set once.
The following parameter changes or checks are carried out from the customer
menu,  10.1.1 "Customer menu",  46.
A three-digit PM code is assigned to the setting options.
Step
PM code Description
1
(00X)
Select the language
2
(00X)
Remember: Prior to installation and commissioning,
read the operating manual!
3
(00X)
Device type information
4
(00X)
Select the make-up variant
5
(00X)
Set the safety valve actuation pressure
6
(00X)
For Magcontrol variant only: Set the minimum
operating pressure P
Otherwise, continue from step 7
7
(00X)
Set the time
8
(00X)
Set the date
9
(00X)
End of the start routine. The stop mode is active.
The system automatically displays the first page of the start routine when you
switch on the device for the first time:
1.
Select the required language and conform your entry with "OK".
Select the corresponding language.
2.
Prior to commissioning, read the operating manual in full and check for
proper assembly.
3.
Confirm your entries via the "OK" button.
42 — English
O
Vacuum spray degassing — 01.04.2022-Rev. D
The start routine moves to the next page.
4.
Select the required Make-up variant and conform your entry with "OK".
For calculation of the make-up variant,  6.4 "Switching and make-
up variants",  37.
5.
Set the safety valve actuating pressure and conform with "OK".

Note!
This step 6 only applies to the Magcontrol make-up variant.
6.
Select the calculated minimum operating pressure and conform with "OK".
For calculation of the minimum operating pressure,  7.2 "Setting
the minimum operating pressure for Magcontrol",  41.
7.
Set the time. The time of an alarm will be stored in the controller's fault
memory.
Use the "Left" and "Right" buttons to select the display value.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".
8.
Set the date. The date of an alarm will be stored in the controller's fault
memory.
Use the "Left" and "Right" buttons to select the display value.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".