Controller
10
Controller
10.1
Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and
active operating mode.
10.1.1 Customer menu
10.1.1.1 Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the
course of initial commissioning, the factory settings must be adjusted for the
system-specific conditions.
Note!
For a description of the operation, 8.1 "Operator panel", 41.
A three-digit PM code is assigned to the setting options
PM
Description
code
001
Select the language
002
Set the time
003
Set the date
004
Select the system type
•
Levelcontrol
•
Magcontrol
minimum operating pressure, 7.2 "Setting the
005
Set the P
0
minimum operating pressure for Magcontrol", 41.
006
Set the actuating pressure for the system safety valve.
–
The actuating pressure protects the device.
Degassing ˃
•
012
Degassing programme
•
Continuous degassing
•
Interval degassing
•
Run-on degassing
•
013
Continuous degassing time
Make-up >
•
Maximum make-up time ...min.
023
•
Maximum make-up cycles ... /2 h.
024
•
Frequency of make-up cycles in 2 hours.
•
024
Make-up pressure
–
Standard = Make-up pressure ˃ 2.3 bar.
–
Setting range 1.3 – 2.3 bar.
–
< 1.3 bar.
•
027
With contact water meter "Yes/'No".
–
If "Yes", continue with 028.
–
If "No", continue with 007.
•
028
Reset make-up quantity "Yes/No".
–
If "Yes", reset to "0".
•
029
Maximum make-up quantity ... l
•
030
Water treatment "Softening / Desalination / None".
–
If "Softening", continue with 031.
–
If "Desalination", continue with the next point
–
If "None", continue with 007.
With conductivity monitoring "Yes/'No".
•
031
Shut off make-up "Yes/No" (if water capacity is exhausted).
•
032
Soft water capacity ... l
–
Calculation required before input.
•
Fillsoft I + softening:
Soft water capacity = 6000 l / hardness reduction.
•
Fillsoft I + desalination:
Soft water capacity = 3000 l / hardness reduction.
•
Fillsoft II + softening:
Soft water capacity = 12000 l / hardness reduction.
•
Fillsoft II desalination:
Soft water capacity = 6000 l / hardness reduction.
46 — English
PM
code
033
034
007
008
10.1.1.2 Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
1.
2.
3.
Vacuum spray degassing — 01.04.2022-Rev. D
Description
•
Hardness reduction ... °dH = GHactual – GHtarget
–
Can be called when softening or desalination is active.
–
Calculate the required reduction in overall hardness
GH before input.
•
replacement interval... months (for softening cartridges
according to manufacturer).
Maintenance interval... months
Floating contact
•
Message selection >
•
Message selection: only messages marked with "√"
are output.
•
All messages: All messages are output.
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
Information >
•
Position of the "PV" 2-way motorized ball valve at the
pressure side of the pump.
–
Position in %
•
Software version
Press "Settings".
–
The controller switches to the setting area.
Press "Customer >".
–
The controller opens the Customer menu.
Press the required area.
–
The controller switches to the selected area.
–
Use the scroll bar to navigate through the list.