Controller
10
Controller
10.1
Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and
active operating mode.
10.1.1 Customer menu
10.1.1.1 Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the
course of initial commissioning, the factory settings must be adjusted for the
system-specific conditions.

Note!
For a description of the operation,  8.1 "Operator panel",  41.
A three-digit PM code is assigned to the setting options
PM
Description
code
001
Select the language
002
Set the time
003
Set the date
004
Select the system type
Levelcontrol
Magcontrol
minimum operating pressure,  7.2 "Setting the
005
Set the P
0
minimum operating pressure for Magcontrol",  41.
006
Set the actuating pressure for the system safety valve.
The actuating pressure protects the device.
Degassing ˃
012
Degassing programme
Continuous degassing
Interval degassing
Run-on degassing
013
Continuous degassing time
Make-up >
Maximum make-up time ...min.
023
Maximum make-up cycles ... /2 h.
024
Frequency of make-up cycles in 2 hours.
024
Make-up pressure
Standard = Make-up pressure ˃ 2.3 bar.
Setting range 1.3 – 2.3 bar.
< 1.3 bar.
027
With contact water meter "Yes/'No".
If "Yes", continue with 028.
If "No", continue with 007.
028
Reset make-up quantity "Yes/No".
If "Yes", reset to "0".
029
Maximum make-up quantity ... l
030
Water treatment "Softening / Desalination / None".
If "Softening", continue with 031.
If "Desalination", continue with the next point
If "None", continue with 007.
With conductivity monitoring "Yes/'No".
031
Shut off make-up "Yes/No" (if water capacity is exhausted).
032
Soft water capacity ... l
Calculation required before input.
Fillsoft I + softening:
Soft water capacity = 6000 l / hardness reduction.
Fillsoft I + desalination:
Soft water capacity = 3000 l / hardness reduction.
Fillsoft II + softening:
Soft water capacity = 12000 l / hardness reduction.
Fillsoft II desalination:
Soft water capacity = 6000 l / hardness reduction.
46 — English
PM
code
033
034
007
008
10.1.1.2 Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
1.
2.
3.
Vacuum spray degassing — 01.04.2022-Rev. D
Description
Hardness reduction ... °dH = GHactual – GHtarget
Can be called when softening or desalination is active.
Calculate the required reduction in overall hardness
GH before input.
replacement interval... months (for softening cartridges
according to manufacturer).
Maintenance interval... months
Floating contact
Message selection >
Message selection: only messages marked with "√"
are output.
All messages: All messages are output.
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
Information >
Position of the "PV" 2-way motorized ball valve at the
pressure side of the pump.
Position in %
Software version
Press "Settings".
The controller switches to the setting area.
Press "Customer >".
The controller opens the Customer menu.
Press the required area.
The controller switches to the selected area.
Use the scroll bar to navigate through the list.