Instelwaarden/ Setting values/ Einstellwerte
STEP NO. DESCRIPTION
Extract fan mode
19
switching input 1
20
Selection input 2
21
Minimum voltage input 2
22
Maximum voltage input 2
Conditions
23
switching input 2
Supply fan mode
24
switching input 2
Extract fan mode
25
switching input 2
26
Geo heat exchanger
Minimum temperature
geo heat exchanger
27
(Below this temperature
the valve opens.)
Maximum temperature
geo heat exchanger
28
(Above this temperature
the valve opens.)
STEP NO. DESCRIPTION
29
RH-sensor
Sensitivity
30
RH-sensor
FACTORY SETTING RENOVENT
SKY PLUS
5
ON
0,0 V
10,0 V
0
5
5
5,0 °C
25,0 °C
FACTORY SETTING RENOVENT
SKY
OFF
0
Renovent Sky 300 Rev F
ADJUSTING RANGE
0 (= Extract fan off)
1
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6
OFF ( = Switching input 2 active)
ON (= 0 - 10 volt input 2 active)
0,0 Volt - 10,0 Volt
0,0 Volt- 10,0 Volt
0 (off)
1 (on)
2 (= On if conditions
3 (= Bypass control)
4 (= Bedroom valve)
0 (= Input fan off)
1
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6
0 (= Extract fan off)
1
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6
OFF (= Valve control geo heat exchanger off)
ON (= Valve control geo heat exchanger on)
0,0 °C - 10,0 °C
15,0 °C - 40,0 °C
ADJUSTING RANGE
OFF (= RH-sensor not active)
ON (= RH-sensor active)
+2 most sensitive
+1
0 default setting RH-sensor
-1
-2 least sensitive
12
GB
STEP
3
/h)
0,5 V
0,5 V
3
/h)
3
/h)
0,5 °C
0,5 °C
STEP
85