Brink Renovent Sky 300 Instructions D'installation page 61

Masquer les pouces Voir aussi pour Renovent Sky 300:
Table des Matières

Publicité

Storing/ Fault/ Störung
Fault
Cause
code
Pressure sensor supply fan
defective.
E100
Red pressure hoses blocked
or "kinked"
Pressure sensor extract fan
defective.
E101
Blue pressure hoses blocked
or "kinked"
E103
Bypass fault .
E104
Extract fan defective.
E105
Supply fan defective.
The temperature sensor that
E106
measures the outdoor tempe-
rature is defective. .
The temperature sensor that
E107
measures the temperature of
the extract air is defective.
If present: The temperature
E108
sensor that measures the ex-
ternal temperature is defective.
If present: The RH-sensor that
E111
measures the huminity is de-
fective.
Dip switches on control board
not set correctly.
Note!
If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way round.
Cut off one of the RJ connectors to the multiple switch and mount a new connector the other way round.
Action appliance
- Switches to constant rpm control.
- The preheater switches on at outdoor
temperatures below 0°C.
- Switches to constant rpm control.
- The preheater switches on at outdoor
temperatures below 0°C
- None.
correctly connected or effective;
wiring or stepper motor)
- Both fans are switched off.
- Preheater is switched off.
- If applicable: Postheater is switched off.
- Restart every 5 minutes.
- Both fans are switched off.
- Preheater is switched off.
- If applicable: Postheater is switched off.
- Restart every 5 minutes.
- Both fans are switched off.
- Preheater is switched off.
- Bypass closes and is blocked.
- Bypass closes and is blocked.
.
- Postheater is switched off.
- If applicable: Geo heat exchanger is
switched off.
- Appliance continues to operate
- Appliance does nothing; red fault LED
on multiple switch is not activated
either.
Renovent Sky 300 Rev F
Action installer
pressure tubes) for fouling, kinking
and damage
pressure tubes) for fouling, kinking
and damage
replace wiring or stepper motor
will automatically be reset.
will automatically be reset.
will automatically be reset.
sensor
sensor
Take the voltage from the appliance.
Replace RH-sensor.
(see § 9).
7
GB
57

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Renovent sky 300 plus

Table des Matières