Helios Ventilatoren
MONTAGE- UND BETRIEBSVORSCHRIFT
INSTALLATION AND OPERATING INSTRUCTIONS
NOTICE DE MONTAGE ET D'UTILISATION
Zentral-Lüftungsgeräte
Central ventilation units
Appareils de ventilation centrale
AIR1 XVP 850-3500
mit Kreuzgegenstrom-Wärmetauscher
with cross-counterflow heat exchanger
avec échangeur de chaleur à contre-courant transversal
DE
EN
FR

Publicité

loading

Sommaire des Matières pour Helios AIR1 XVP Serie

  • Page 1 Helios Ventilatoren MONTAGE- UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D’UTILISATION Zentral-Lüftungsgeräte Central ventilation units Appareils de ventilation centrale AIR1 XVP 850-3500 mit Kreuzgegenstrom-Wärmetauscher with cross-counterflow heat exchanger avec échangeur de chaleur à contre-courant transversal...
  • Page 2 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP DEUTSCH INHALTSVERZEICHNIS KAPITEL 1 ALLGEMEINE HINWEISE ������������������������������������������������������������������������������������������������������������������� SEITE 2 Wichtige Informationen ........................... Seite 2 Warn- und Sicherheitshinweise ......................Seite 2 Garantieansprüche – Haftungsausschluss ....................Seite 2 Vorschriften/Richtlinien ........................... Seite 2 Einsatzbereich – Bestimmungsgemäße Verwendung ................Seite 2 KAPITEL 2 INSTALLATION UND INBETRIEBNAHME ������������������������������������������������������������������������������������������...
  • Page 3 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP KAPITEL 3 TECHNISCHE DATEN ���������������������������������������������������������������������������������������������������������������������� SEITE 39 Technische Daten ..........................Seite 39 Geräteübersicht ........................... Seite 40 Abmessungen ............................. Seite 41 Leistungskennlinien ..........................Seite 42 KAPITEL 4 FUNKTIONEN UND EINSTELLUNGEN ������������������������������������������������������������������������������������������� SEITE 42 Betriebsmodi ............................Seite 42 4.1.1 Manueller Betrieb ..........................
  • Page 4 Wenn die nachfolgenden Ausführungen nicht beachtet werden, entfällt die Gewährleistung. Gleiches gilt für Haftungs- ansprüche an den Hersteller. Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht statthaft. Even tuell auftretende Schäden unterliegen nicht der Gewährleistung.
  • Page 5 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Anwendungsbeschränkungen der AIR1 XVP.. Geräte sind aus der folgenden Tabelle ersichtlich: AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP 1250 1800 2500 3500 Umgebungstemperatur 0 - 50 °C 0 - 50 °C 0 - 50 °C 0 - 50 °C 0 - 50 °C...
  • Page 6 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP toren). Der Lagerort muss erschütterungsfrei, wassergeschützt und frei von übermäßigen Temperaturschwankungen sein. Schäden, deren Ursprung in unsachgemäßem Transport, unsachgemäßer Einlagerung oder Inbetriebnahme liegen, sind nachweisbar und unterliegen nicht der Gewährleistung. 2�2 Transport Der Transport muss sorgfältig durchgeführt werden. Es wird empfohlen das Gerät bis zur Aufstellung in der Original- verpackung zu belassen, um mögliche Beschädigungen und Verschmutzungen zu vermeiden.
  • Page 7 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Wird das Gerät mit einem Kran transportiert, müssen die Transportrahmenlöcher im Grundrahmen verwendet werden (s. Abb.3). 1. Transportgestänge durch die Löcher im Grundrahmen führen. 2. Die Transportgestänge mit den Schrauben sicher befestigen. 3. Kette oder Seil bis zum Ende des Transportgestänges führen. 4.
  • Page 8 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2�3�1 Entsorgung Lebensgefahr durch elektrischen Stromschlag! GEFAHR Ein elektrischer Stromschlag kann zu Tod oder schweren Verletzungen führen� – Sicherstellen, dass das Gerät spannungsfrei und isoliert ist. Gerät erden und kurzschließen, benachbarte spannungs- führende Komponenten abschirmen. Alle Komponenten und Filter sowie ausgediente Betriebsmittel (z.B.
  • Page 9 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP A: Mindestabstand für die Wartung oberhalb des Geräts B: Tiefe des Geräts C: Mindestabstand für die Wartung vor dem Gerät D: Höhe des Lüftungsgeräts (inkl. Klemmenkasten) Abb�4 Type Maße (mm) A (mm) B (mm) C (mm) D (mm) AIR1 XVP 850 1085 1596...
  • Page 10 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Vorhandene Abflusssysteme dürfen nicht direkt an das Abwasserkanalsystem angeschlossen werden. ACHTUNG Der Kondensatverschluss muss vor der Inbetriebnahme entfernt werden! Kugelsiphon als Zubehör verfügbar. HINWEIS 1. Das Kondensatrohr wird im Folgenden dargestellt (s. Abb.6). Abb�6 2.
  • Page 11 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 4. Die Türen mit dem im Lieferumfang enthaltenen Schlüssel entriegeln und die Türen öffnen (s. Abb.9). Abb�9 5. Den Kondensatverschluss mit einem Schraubendreher entfernen (s. Abb.10). Abb�10 6. Den Kondensatverschluss von der Schraube lösen und die Schraube mit einem Schraubendreher festziehen (s. Abb.11).
  • Page 12 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Abb�14 Gerätetype Maße (mm) AIR1 XVP 2500 520 AIR1 XVP 3500 720 n: Anzahl der Bohrungen Loch-/Bolzenmaß: M8 x 16 – Den Kanal, das Übergangsstück und das flexible Kanalverbindungsstück in den Ecken des Geräts mit Schrauben HINWEIS M8 x 16 anschrauben (AIR1 XVP 2500/3500).
  • Page 13 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3. Den Filter einsetzen und verriegeln wie unten gezeigt (s. Abb.17). ACHTUNG Die Filterklasse muss im Inbetriebnahme-Assistent eingestellt werden (s. Kap. 2.11). Abb�17 2�9 Elektrischer Anschluss Vor allen Wartungs- und Installationsarbeiten oder vor Öffnen des Klemmenkastens ist das Gerät allpolig vom GEFAHR Netz zu trennen! Der elektrische Anschluss darf nur von einer autorisierten Elektrofachkraft entsprechend den nachstehenden Anschlussplänen ausgeführt werden�...
  • Page 14 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2�9�1 Geräteinterne Elektroanschlüsse Die geräteinternen Elektroanschlüsse sind mit Schutzkappen gesichert, vor dem Anschluss wie in Abb.18 gezeigt Schutzkappen entfernen. Abb�18 2�9�2 Befestigung und Anschluss des Hauptschalters Der Hauptschalter ist Teil des Lieferumfangs und liegt dem Beipack bei (siehe Kap. 2.1.1 „Sendungsannahme“). Bei den Baureihen AIR1-XVP 850 - 1800 wird der Hauptschalter (➊) oben montiert.
  • Page 15 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3. Das Hauptschaltergehäuse öffnen (s. Abb.22). Leitungsquerschnitt, der für den Stromanschluss verwendet wird, überprüfen. Abb�22 4. Kabelverschraubung lösen und Leitung (Versorgungsleitung sowie Leitung von Hauptschalter zu Elektro-Anschluss- kasten im Gerät) durchführen. Leitungen an die Klemmen anschließen (s. Abb.23). Die Verbindungen sind dem Anschlussplan zu entnehmen.
  • Page 16 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2. Abdeckung des Klemmenkastens öffnen (s. Abb.26a). 3. Leitungsquerschnitt, der für den Stromanschluss verwendet wird, überprüfen (siehe Anschlussplan). 4. Netzleitung in das Gerät einführen (s. Abb.26b, c). Abb�26     5. Kabel mit den markierten Anschlusspunkten verbinden (s. Anschlussplan). Abb�27 2�9�4 Anschluss Bedienelement Lebensgefahr durch elektrischen Stromschlag!
  • Page 17 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 4. Das andere Ende der Leitung am Bedienelement anschließen (s. Anschlussplan). Abb�30 AIR1 BE-ECO AIR1 BE-TOUCH 2 2�9�5 Modbus/Bacnet Die AIR1 XVP Lüftungsgeräte haben einen rs485-Anschluss und einen Ethernet-Anschluss. Der rs485-Anschluss wird für die interne Kommunikation der Drucksensoren verwendet. Der Ethernet-Anschluss kann für die Kommunikation mit der Gebäudeleittechnik verwendet werden.
  • Page 18 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2�10 Anschlusspläne AIR1-XVP 850 Haupt-Anschlussplan SS-1506...
  • Page 19 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 850 Elektrische Vorheizung/ Nachheizung SS-1516...
  • Page 20 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1250 Haupt-Anschlussplan SS-1507...
  • Page 21 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1250 Elektrische Vorheizung/ Nachheizung SS-1517...
  • Page 22 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1250 Elektrische Vorheizung SS-1518...
  • Page 23 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1800 Haupt-Anschlussplan SS-1508...
  • Page 24 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1800 Elektrische Vorheizung/ Nachheizung SS-1519...
  • Page 25 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 2500 Haupt-Anschlussplan SS-1509...
  • Page 26 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 2500 Elektrische Vorheizung/ Nachheizung SS-1520...
  • Page 27 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 3500 Haupt-Anschlussplan SS-1510...
  • Page 28 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 3500 Elektrische Vorheizung/ Nachheizung SS-1521...
  • Page 29 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Inbetriebnahme Assistent 2�11 Inbetriebnahme-Assistent (Wizard) Die wichtigsten Lüftungsgeräteeinstellungen können mit Hilfe des Inbetriebnahme-Assistenten (Wizard) vorgenommen werden (ausgenommen Einregulierung, Notfallbetrieb, Zeit/Datum, Schaltuhr). Das Bedienelement öffnet während der Erstinbetriebnahme automatisch den Inbetriebnahme-Assistenten und startet mit der Sprachauswahl. Falls die Einstellungen später geändert werden müssen (ausgenommen Sprachauswahl, Schaltuhr, Temperatur und Lüftungs-Sollwerte), muss der Inbetriebnahme-Assistent (Wizard) erneut aufgerufen werden.
  • Page 30 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2�11�2 Aufrufen des Inbetriebnahme-Assistenten (Wizard) Schritt 1: Als Admin einloggen (Zugriffsrechte) ↑ Ventilatorregelung Schaltuhr → Zugriffsrechte ↓ → Einloggen Ausloggen Codeänderung Einloggen Code eingeben 1111 Ggw Bedienebene: Keine Schritt 2: Assistenten (Wizard) aktivieren Taste drücken, um zum Hauptmenü zurückzugelangen. Die Taste drücken, um zum Menü...
  • Page 31 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Es kann nur ein Lüftungsgerät ausgewählt werden. Das Wort “Kein” erscheint automatisch in den anderen beiden Gruppen. Die letzte Einstellung ist gültig. ↑ AIR1 XVP Serie Wähle Gerätegröße ↓ Nicht zutreffend Gerät wählen: Beispiel: ↑...
  • Page 32 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Beispiel: Außenlufttemperatur [°C] Zulufttemperatur [°C] ↑ Temperatur-Regel-Modus Außenl abh Zuluft-R ↓ Außenl abh Soll-Wer ↑ -20.0 °C = 25.0 °C -15.0 °C = 24.0 °C ↓ -10.0 °C = 23.0 °C Außenl abh Soll-Wer ↑...
  • Page 33 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Der Sollwert wird im Menü „Temperatur“ angezeigt (als Benutzer oder Admin einloggen): ↑ Temperatur-Regel-Modus Abluft-Temp Kask-R ↓ ↑ Abluft-Temperatur Soll: XX.X °C ↓ e� Außentemperaturabhängiges Umschalten zwischen Raum- und Zuluftregelung HINWEIS Nur mit dem als Zubehör erhältlichen Feuchte-Temperatur-Fühler AIR1/KWL-FTF 0-10V möglich. Den Analogausgang A2 (Temperatursignal) des AIR1/KWL-FTF 0-10V an den Analogeingang AI2 des Lüftungsgeräts anschließen (s.
  • Page 34 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Raumtemperatur kann angepasst werden, wenn die Außentemperatur steigt. Zum Beispiel kann bei höheren Außentemperaturen eine etwas höhere Raumtemperatur akzeptabel sein, bzw. bei kühler Witterung eine etwas niedri- gere Raumtemperatur. Diese Funktion dient dem Energiesparen. Der Sollwert der Raumtemperatur wird außentemperaturabhängig mittels einer Regelungskurve mit 8 Punkten kom- pensiert.
  • Page 35 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2�11�7 Lüftungsmodus Der Lüftungsmodus wird während der Inbetriebnahme festgelegt. Diese Einstellung kann später nur im Inbetriebnahme- Assistenten (Bedienebene Admin) verändert werden. Die folgenden Lüftungsmodi sind vorhanden: • Konstanter Volumenstrom • Konstante Drehzahl • Konstanter Druck •...
  • Page 36 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP c� Konstanter Druck Nur mit dem als Zubehör erhältlichen Drucksensor AIR1-CAP möglich. Die Installation ist im Zuluft- oder im Abluftkanal HINWEIS möglich. Eine Lüftungsstufe ist möglich: • Normal Wird im späteren Betrieb die Lüftungsstufe minimal oder intensiv gewählt, läuft das Lüftungsgerät jeweils mit den Ein- stellungen für die Lüftungsstufe normal.
  • Page 37 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP • ePM1 55 % (F7) Eine entsprechende Filterdruckverlustkurve ist für jeden Filtertyp hinterlegt. Der Filter-/Wartungsalarm wird ausgelöst, wenn der Filterdruckverlust höher ist als zulässig, unabhängig vom gewählten Betriebspunkt. Nach dem Filterwechsel, schaltet der Alarm automatisch ab. ↑...
  • Page 38 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Taste drücken, um in das Menü „Außentemp-Bypass“ zu gelangen. Die Taste und die Taste drücken, um die oberen und unteren Grenzwerte der Außenlufttemperatur für die Nachtkühlung festzulegen. Bei Über- oder Unter- schreiten der Grenzwerte, wird der Bypassbetrieb automatisch beendet. Bypass aktiv zwischen ↑...
  • Page 39 Funktion deaktiviert. Der Brandmodus wird durch die Schließung des Schaltkontaktes DI2 aktiviert. Auswahl Normal offen Normal geschlossen 2�13 Einregulierung Die Einregulierung wird nach Abschluss des Inbetriebnahme-Assistenten im Hauptmenü durchgeführt. Sie erfolgt über das Untermenü „Ventilatorregelung“. Helios Ventilatoren 2019-XX-XX 09:30 System: Abgeschaltet SW: 19.5 Ist: 0.0 °C Betriebsmodus Temperatur Ventilatorregelung...
  • Page 40 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Je nach gewählter Betriebsart („Konstanter Volumenstrom“, „Konstanter Druck“, „Konstante Drehzahl“) sind folgende Einstellungen vorzunehmen: a� Konstant Volumenstrom • Volumenstromregelung ZV (Zuluftventilator) • Intensiv xxx [m³/h] • Normal xxx [m³/h] • Minimal xxx [m³/h] • Volumenstromregelung AV (Abluftventilator) •...
  • Page 41 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP KAPITEL 3 3�1 Technische Daten TECHNISCHE Die mechanischen Verbindungen müssen korrekt ausgeführt sein, um den maximalen Wirkungsgrad des Geräts zu DATEN erreichen. Der thermische Wirkungsgrad, der Schallpegel und die elektrische Leistung des Geräts können je nach den Umgebungsbedingungen, unter denen das Gerät betrieben wird, variieren.
  • Page 42 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3�2 Geräteübersicht AIR1 XVP 850-1800 Abb�31 AIR1 XVP 2500-3500 Abb�32 Hauptschalter Außenluftvorfilter (ePM10 50% /optional) Fortluft Abluftfilter (ePM10 50%) Außenluft Warmwasser-/elektrische Nachheizung (optional) Abluft Bypassklappe Zuluft Kreuzgegenstrom-Wärmetauscher Durchführungen für Warmwasser-Nachheizung Abluft-/Fortluftventilator 17 16 Klemmenkasten Zuluft-/Außenluftventilator Elektrische Vorheizung Kondensatwanne...
  • Page 43 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3�3 Abmessungen AIR1-XVP 850- 1800 Abb�33 ø32 ODA - Outdoor Air / Außenluft / Air extérieur EHA - Exhaust Air / Fortluft /Air rejeté ETA - Extract Air / Abluft / Air repris SUP - Supply Air / Zuluft / Air soufflé Art.Nr.
  • Page 44 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3�4 Leistungskennlinien AIR1-XVP 850 AIR1-XVP 1250 Δp Δp V · (m³/h) V · (m³/h) 1000 1200 1400 750 1000 1250 1500 1750 2000 AIR1-XVP 1800 AIR1-XVP 2500 Δp Δp 1200 1000 V · (m³/h) V ·...
  • Page 45 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP • Intensiv • Aus (Standby) Nach Auswahl der manuellen Betriebsart, lauft das Lüftungsgerät mit den eingestellten Sollwerten für die jeweilige Stufe. m Lebensgefahr durch elektrischenStromschlag! GEFAHR Ein elektrischer Stromschlag kann zu Tod oder schweren Verletzungen führen. Das Gerät steht auch nach der Auswahl „Aus“...
  • Page 46 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Prioritäten der Schaltuhr (höchste Priorität zuerst): • Timer Intensiv • Timer Normal oder VOD (höherer Lüftungsbedarf) • Timer Minimal • Timer Umluftregelung Überschneiden sich die eingestellten Zeiten der Schaltuhren, z.B. wenn der Timer „Intensiv“ und der Timer „Normal“ für die gleiche Zeit programmiert werden, dann wird der Timer mit der höheren Priorität aktiviert und das Lüftungsgerät wird auf der Lüftungsstufe „Intensiv“...
  • Page 47 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP VOD Stoppzeit: Sobald das Lüftungsgerät auf der Lüftungsstufe „intensiv“ länger als 2 Stunden betrieben wurde, wird der sensorgeführte Betrieb für die eingestellte Nachlaufzeit beendet. 0 Stunden bedeutet, dass der sensorgeführte Betrieb aufgrund einer hohen Sensoranforderung nie beendet wird. →...
  • Page 48 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Festlegen der Nachlaufzeit: • Als Benutzer oder Admin einloggen • Das Menü „Schaltuhr“ aufrufen • Das Menü „Nachlauf“ aufrufen • Die gewünschte Nachlaufzeit festlegen Nachlauf XXX min Zeit in Nachlauf XXX min 4�1�6 Weitere Betriebseinstellungen Im Hauptmenü...
  • Page 49 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP • Stetige Leistungsregelung der Vorheizung bis eine Fortlufttemperatur von +4 °C oder 100 % der Leistung erreicht wird. • Sobald die Vorheizung für mehr als 3 Minuten mit einer Leistung von 100 % angesteuert wird, reduziert sich der Gesamtvolumenstrom (Zu- und Abluft) stetig um max.
  • Page 50 Tastendruck, stellen sich alle Benutzerebenen automatisch auf „Keine Rechte” zurück. Alle Passwörter können im Menü „Zugriffsrechte“ unter „Code ändern“ geändert werden. Wurde das Admin-Passwort geändert und dann vergessen, kann ein temporäres Master-Passwort von Helios angefor- dert werden (Helios Kundendienst).
  • Page 51 Montage- und Betriebsvorschrift Hauptmenü Zentral-Lüftungsgeräte AIR1 XVP Helios Ventilatoren AIR1 XVP 850 Programm Lüft.system EXOreal C Version Choose Language 2023-06-22 09:30 Cross Counter Flow U Version: 3.7-0-51 3.5-1-04 Sprachauswahl System: Gestoppt 2023-04-16 SVN Build German SW: 20.0 Ist: 0.0°C ID Nr: 011902011871 4364 Hauptmenü...
  • Page 52 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs vom Hauptmenü (Teil 2 von 2) 7. Eingänge / Ausgänge 9. Einstellungen AI1: 0.0 Inaktiv Temp.regelung Zuluftregelung AI Erweit 3 AI2: 45.5 Feuchte Volumenstromregl P-Band: 33.0 °C AI Erweit 4 AI3: 0.0 Inaktiv Alarmeinstellungen I-Zeit: 100.0 s AI4: 0.0 Inaktiv...
  • Page 53 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 1 von 4) System Kommunikation Umluftregelung Choose Language Erweiterungseinh 1 Temp.regl bei Konstanter oder Kommunikationsport1 Sprachauswahl Keine Umluft Offset-Sollwert Erw und FU/Druck German Erweiterungseinh 2 erlauben: bei Umluft Keine Heizen &...
  • Page 54 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 2 von 4) Eingänge / Ausgänge Sensoreinstell AI1: Zuluftdruck bei AI1... AI Erweit 3 Sign: Inaktiv 0.0V: 0.0 AI Erweit 4 Rohwert: NaN 10.0V: 500.0 Pa Fühlerkorr: 0.0 Filterfaktor: 0.2 Pressure A Erweit 3 Abluftdruck bei UI Erweit 3...
  • Page 55 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 3 von 4) ü Pumpensteuerung Funktion BSK: Freie Nachtkühl P1-Erhitzer Pumpenstopp: Ja Inaktiv Aktiv: Ja P1-WRG Ausschaltverz: 1 Min Betrieb bei Alarm Außentemp aktiv P1-Kühler Außent Stop: 0°C Gestoppt 22 °C Differenz: 1.0 Ventilatorstufe bei...
  • Page 56 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 4 von 4) Stufenregler fi Stufenregl Erhitz Stufenregl Erhitz Start Stufe 1: 10 % Alarm Nr(1-125): 1 Fehler Zuluftventila Verzögerung Stufenregl Kühler Sequentiell Stopp Stufe 1: 5 % Fehler Zuluftventila Priorität: B-Alarm Zuluftventilator Start Stufe 2: 45 %...
  • Page 57 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP KAPITEL 5 5�1 Service und Wartung SERVICE UND Der Filterwechsel erfolgt in der Regel durch den Anwender. Zusätzliche Reinigungs- und Wartungsarbeiten dürfen nur WARTUNG von einer Elektrofachkraft durchgeführt werden. Lebensgefahr durch elektrischen Stromschlag! Vor allen Wartungs- und Installationsarbeiten sowie vor Öffnen des Klemmenkastens ist das Gerät allpolig vom GEFAHR Netz zu trennen! Gefährdung durch elektrischen Stromschlag, bewegliche Teile (Ventilatoren) und ggf�...
  • Page 58 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 5�3 Service und Wartung des Kreuzgegenstrom-Wärmetauschers Lebensgefahr durch elektrischen Stromschlag! GEFAHR Vor allen Wartungs- und Installationsarbeiten sowie vor Öffnen des Klemmenkasten ist das Gerät allpolig vom Netz zu trennen! Gefährdung durch elektrischen Stromschlag, bewegliche Teile (Gebläse) und heiße Oberflächen� Verletzungsgefahr! WARNUNG Wärmetauscher haben ein hohes Gewicht und können Kondensatwasser enthalten!
  • Page 59 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3. Das Profil sorgfältig entfernen (s. Abb.39). Abb�39 4. Den Wärmetauscher demontieren (s. Abb.40). Abb�40 5. Die Klappen entfernen (s. Abb.41). Abb�41 5�3�2 Reinigung des Kreuzgegenstrom-Wärmetauschers Der Kreuzgegenstrom-Wärmetauscher muss regelmäßig auf Schmutz und Staubablagerungen überprüft werden. Zusätzlich muss der Kreuzgegenstrom-Wärmetauscher alle 6 Monate auf Schäden überprüft werden.
  • Page 60 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die technischen Daten der Standard-Filter sind in der Tabelle ersichtlich: Filter Nenn-Luft- Anzahl Filterklasse Abmessungen Empfohlene volumen- Filter (LxHxB) (mm) Enddruck- strom (m³/h) differenz (Pa) AIR1 XVP 850 Abluftfilter ePM10 50 % 312 x 678 x 96 AIR1 XVP 850 Außenluftfilter ePM1 55 % 312 x 678 x 96...
  • Page 61 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Der Ventilator muss alle 6 Monate auf Schmutz, Schäden und Korrosion überprüft werden: – Regelmäßige Inspektion, ggf. mit periodischer Reinigung ist erforderlich, um Unwucht durch Verschmutzung zu ver- meiden. – Das Ventilatorgehäuse reinigen. – Vibrations- und schwingungsfreier Betrieb sind zu gewährleisten. –...
  • Page 62 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2. Kondensatwanne mit einem Tuch reinigen (s. Abb.48). Abb�48 5�7 Reinigung der Gehäuse Lebensgefahr durch elektrischen Stromschlag! GEFAHR Vor allen Wartungs- und Reinigungsarbeiten das Gerät allpolig vom Stromnetz trennen� Verletzungsgefahr durch elektrischen Schlag, bewegliche Teile (Gebläse) und heiße Oberflächen� –...
  • Page 63 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP h� Funktionen Außenluftklappe • Auto = Die Außenluftklappe wird automatisch vom Regler geöffnet und geschlossen, wie im normalen Betrieb des Lüftungsgeräts. • Schließen = Die Außenluftklappe wird nicht angesteuert und schließt über Federrücklauf. • Öffnen = Die Außenluftklappe wird angesteuert und öffnet. i�...
  • Page 64 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Alarm Priorität Stopp Alarmbeschreibung und -behandlung Alarme Temperatur Fehler Zuluftregelung Nein • Differenz SOLL-/IST-Temperatur ist für 30 Minuten größer als 5 K • Sollwert ist unrealistisch prüfen • Optionale Heizung/Kühlregister prüfen • Mischer der optionalen Hydraulikeinheit prüfen •...
  • Page 65 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Alarm Priorität Stopp Alarmbeschreibung und -behandlung Hand P1 Wärmetauscher Nein • Pumpe Wärmetauscher • Steuerung über Betriebsmodus manuell Hand P1 Kühler Nein • Pumpe Kaltwasser-Kühlregister • Steuerung über Betriebsmodus manuell Handbetrieb Extra Sequenz Y4 Nein •...
  • Page 66 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Alarm Priorität Stopp Alarmbeschreibung und -behandlung Komm. Übertragungsfehler Nein • Kommunikation zu ..unterbrochen • Modbus-Verdrahtung von Druckfühler zur Steuerung prüfen Weitere Alarme Feueralarm Sofern der Alarm unberechtigt: • Anschluss an Klemmleiste prüfen (bauseitiger Kontakt) •...
  • Page 67 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Zubehör (AIR1-XVP 850) Bestell-Nr� ELF-AIR1 XVP 850/ePM10 50%/48 Vorfilter Außenluft 40515 ELF-AIR1 XVP 850/ePM11 80%/96 Filter Außenluft 40517 AIR1-EVH XVP 850 Elektrische Vorheizung (Schütz) 40473 Elektrische Nachheizung (Schütz) 40474 AIR1-ENH XVP 850 AIR1-NH WW XVP 850 Warmwasser Nachheizung (Ventil) 40475 AIR1-KR KW XVP 850 L...
  • Page 68 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Zubehör (AIR1-XVP 3500) Bestell-Nr� ELF-AIR1 XVP 3500/ePM10 50%/48 Vorfilter Außenluft 40531 ELF-AIR1 XVP 3500/ePM11 80%/96 Filter Außenluft 40533 AIR1-EVH XVP 3500 Elektrische Vorheizung (Schütz) 40507 AIR1-ENH XVP 3500 Elektrische Nachheizung (Schütz) 40508 AIR1-NH WW XVP 3500 Warmwasser Nachheizung (Ventil) 40509 AIR1-KR KW XVP 3500 L...
  • Page 69 EU Declaration of Conformity to EC Machinery Directive 2006/42/EC Annex II Part 1A / Déclaration de conformité UE selon la Directive CE relative aux machines 2006/42 Note II Partie 1A Helios Ventilatoren GmbH + Co KG Lupfenstr. 8, D-78056 Villingen-Schwenningen Hiermit erklären wir, dass die Produkte in Übereinstimmung mit den untenstehenden Richtlinien entwickelt,...
  • Page 70 Installation and Operating Instructions Central ventilation units AIR1 XVP ENGLISH TABLE OF CONTENTS CHAPTER 1 GENERAL INFORMATION ���������������������������������������������������������������������������������������������������������������� PAGE 2 Important information ..........................Page 2 Warning and safety instructions ......................Page 2 Waranty claims– Exclusion of liability ....................... Page 2 Regulations - Guidelines .........................
  • Page 71 Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 3 TECHNICAL DATA ������������������������������������������������������������������������������������������������������������������������� PAGE 39 Performance and technical data ......................Page 39 Unit overview ............................Page 40 Dimensions ............................Page 41 Performance curves ..........................Page 42 CHAPTER 4 FUNCTIONS AND SETTINGS ������������������������������������������������������������������������������������������������������� PAGE 42 Operating modes ..........................
  • Page 72 If the preceding instructions are not observed, all warranty claims shall be excluded. This also applies for liability claims against the manufacturer. The use of accessories, which are not recommended or offered by Helios, is not permitted. Any possible damages are not covered by the warranty.
  • Page 73 Installation and Operating Instructions Central ventilation units AIR1 XVP The AIR1 XVP.. unit application limits can be seen in the following table:: AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP 1250 1800 2500 3500 Ambient temperature 0 - 50 °C 0 - 50 °C 0 - 50 °C 0 - 50 °C...
  • Page 74 Installation and Operating Instructions Central ventilation units AIR1 XVP +40 °C). Damages due to improper transportation, storage or commissioning must be verified and are not liable for warranty. 2�2 Shipping The shipping must be carried out carefully. It is recommended to leave the unit in the original packaging until installation to avoid possible damages and contamination.
  • Page 75 Installation and Operating Instructions Central ventilation units AIR1 XVP If the unit is transported with a crane, the transportation frame holes in the base frame must be used (see Fig.3). 1. Lead the transportation rods through the holes in the base frame. 2.
  • Page 76 Installation and Operating Instructions Central ventilation units AIR1 XVP 2�3�1 Disposal Danger to life due to electric shock! DANGER An electric shock can result in death or serious injury� – Ensure that the unit is voltage-free and isolated from the mains power supply. Ground and short circuit the unit, shield neighbouring live components Dispose of all components and filters and disused operating materials (e.g.
  • Page 77 Installation and Operating Instructions Central ventilation units AIR1 XVP A: Minimum distance for servicing above the unit B: Depth of unit C: Minimum distance for servicing in front of the unit D: Height of unit (incl. terminal box) Fig�4 Type Dimensions (mm) A (mm) B (mm) C (mm) D (mm) AIR1 XVP 850...
  • Page 78 Installation and Operating Instructions Central ventilation units AIR1 XVP ATTENTION The condensate cap must be removed before commissioning! Ball siphon available as an accessory� NOTE 1. The condensation outlet pipe is shown below (see Fig.6). Fig�6 2. Attach the pipe bracket (see Fig.7). Fig�7 3.
  • Page 79 Installation and Operating Instructions Central ventilation units AIR1 XVP 4. Unlock and open the doors with the key included in the scope of delivery (see Fig.9). Fig�9 5. Remove the condensate cap with a screwdriver (see Fig.10). Fig�10 6. Unscrew the condensate cap from the screw and tighten the screw with a screwdriver (see Fig.11). Fig�11 2�7 Flange connection / adapters...
  • Page 80 Installation and Operating Instructions Central ventilation units AIR1 XVP Fig�14 Unit type Dimensions (mm) AIR1 XVP 2500 520 AIR1 XVP 3500 720 n: Number of drill holes Hole/screw dimensions: M8 x 16 – Fasten the duct, connecting piece and flexible duct connector in the corners of the unit with screws M8x16 (AIR1 NOTE XVP 2500/3500).
  • Page 81 Installation and Operating Instructions Central ventilation units AIR1 XVP 3. Insert and lock the filter as shown below (see Fig.17). ATTENTION The filter class must be adjusted in the commissioning assistant (see chap. 2.11). Fig�17 2�9 Electrical connection The unit must be fully isolated from the mains power supply before all maintenance and installation work and DANGER opening the terminal compartment! The electrical connections must be carried out in accordance with the relevant wiring diagram and must only be carried out by qualified electricians�...
  • Page 82 Installation and Operating Instructions Central ventilation units AIR1 XVP 2�9�1 Internal electrical connections The internal electrical connections of the device are secured with protective caps, remove the protective caps before connection, see Fig. 18. Fig�18 2�9�2 Fixing the main switch The main switch is part of the scope of delivery and is included in the accessory pack (see chap.
  • Page 83 Installation and Operating Instructions Central ventilation units AIR1 XVP 3. Open the main switch housing (see Fig.22). Check the thickness of the cable to be used for power connection. Fig�22 4. Loosen the grommet and insert the cables (supply line and line from main switch to electrical junction box in the unit).
  • Page 84 Installation and Operating Instructions Central ventilation units AIR1 XVP 2. Open the terminal box cover (see Fig.26a). 3. Check the thickness of the cable to be used for power connection (see wiring diagram). 4. Insert the power cable into the unit (see Fig.26b, c). Fig�26 5.
  • Page 85 Installation and Operating Instructions Central ventilation units AIR1 XVP 4. Connect the other end of the HMI cable to the display (see wiring diagram). Fig�30 AIR1 BE-ECO AIR1 BE-TOUCH 2 2�9�5 Modbus/Bacnet AIR1 XVP.. units have a rs485 connection and Ethernet connection. The rs485 connection is used for the internal com- munication of the pressure sensors.
  • Page 86 Installation and Operating Instructions Central ventilation units AIR1 XVP 2�10 Wiring diagrams AIR1-XVP 850 Main wiring diagram SS-1506...
  • Page 87 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 850 Electrical preheater/ afterheater SS-1516...
  • Page 88 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1250 Main wiring diagram SS-1507...
  • Page 89 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1250 Electrical preheater/ afterheater SS-1517...
  • Page 90 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1250 Electrical preheater SS-1518...
  • Page 91 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1800 Main wiring diagram SS-1508...
  • Page 92 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1800 Electrical preheater/ afterheater SS-1519...
  • Page 93 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 2500 Main wiring diagram SS-1509...
  • Page 94 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 2500 Electrical preheater/ afterheater SS-1520...
  • Page 95 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 3500 Main wiring diagram SS-1510...
  • Page 96 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 3500 Electrical preheater/ afterheater SS-1521...
  • Page 97 Installation and Operating Instructions Central ventilation units AIR1 XVP Inbetriebnahme Assistent 2�11 Commissioning assistant (wizard) The most important ventilation unit settings can be adjusted using the commissioning assistant (wizard) (except for adjustment, emergency operation, time/date, timer). The controller will automatically open the commissioning assistant during the initial commissioning and starts with the language selection.
  • Page 98 Installation and Operating Instructions Central ventilation units AIR1 XVP 2�11�2 Calling up the commissioning assistant (wizard) Step 1: Log in as Admin (Access rights) ↑ Fan control Timer → Access rights ↓ → Log on Log off Change password Log on Enter password 1111 Actual level: None Step 2: Activate assistant (wizard)
  • Page 99 Installation and Operating Instructions Central ventilation units AIR1 XVP → • Central ventilation units AIR1 XVP.. AIR1 XVP Serie Only one ventilation unit can be selected. The word “None” appears automatically in the other two windows. The last setting is valid. ↑...
  • Page 100 Installation and Operating Instructions Central ventilation units AIR1 XVP The supply air temperature setpoint is compensated for depending on the outdoor temperature using a control curve with 8 points. Example: Outdoor temp� [°C] Supply air temp� [°C] ↑ Temp. control mode Outdoor comp supply ↓...
  • Page 101 Installation and Operating Instructions Central ventilation units AIR1 XVP The setpoint is displayed in the “temperature” menu (log in as User or Admin): Temp. control mode ↑ Cascade extract ctrl ↓ ↑ Extract air temp. Setp: XX.X °C ↓ e� Outdoor Temperature Dependent Supply or Room Temperature Control NOTE Only possible with the humidity-temp.
  • Page 102 Installation and Operating Instructions Central ventilation units AIR1 XVP The room temperature can be adapted when the outside temperature rises. For example, a slightly higher room tem- perature may be acceptable at higher outside temperatures, or a slightly lower room temperature in cooler weather conditions.
  • Page 103 Installation and Operating Instructions Central ventilation units AIR1 XVP 2�11�7 Ventilation mode The ventilation mode is set during commissioning. This setting can be modified later using the commissioning assistant (operating level Admin) only. The following ventilation modes are available: • Constant volume flow •...
  • Page 104 Installation and Operating Instructions Central ventilation units AIR1 XVP c� Constant pressure Only possible with pressure sensor AIR1-CAP accessory. Installation in the supply air or extract air duct is possible. NOTE One ventilation stage is possible: • Normal If the ventilation stage reduced or boost is subsequently selected, the ventilation unit will run with the settings for the ventilation stage normal.
  • Page 105 Installation and Operating Instructions Central ventilation units AIR1 XVP Press the button to enter the “Extract air filter type” menu. Press the button to select filter type extract air and confirm by pressing the button. 2�11�11 Auxiliary heater type Selection of available auxiliary heater types. The following selection options are available: •...
  • Page 106 Installation and Operating Instructions Central ventilation units AIR1 XVP The start and end times for night cooling are set in the “Bypass active between” menu. Press the button and the button to enter the start and end times. Confirm by pressing the button.
  • Page 107 Normally closed 2�13 Adjustment The adjustment is carried out in the main menu after completing the commissioning assistant. It is carried out under the submenu “Fan control”. Helios Ventilatoren 2019-XX-XX 09:30 System: Deactivated Target: 19.5 Actual: 0.0 °C Operating mode...
  • Page 108 Installation and Operating Instructions Central ventilation units AIR1 XVP b� Constant pressure • Pressure regulation SAF (supply air fan) • Target: xxx [Pa] The supply air fan and extract air fan are automatically set to the same pre-set duct pressure level using the volume NOTE flow measurement.
  • Page 109 Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 3 3�1 Performance and technical data TECHNICAL DATA Mechanical connections must be made correctly in order to achieve the maximum unit efficiency. The thermal efficiency, sound level and electrical performance of the unit may vary depending on the environmental conditions under which the unit is operated.
  • Page 110 Installation and Operating Instructions Central ventilation units AIR1 XVP 3�2 Unit overview AIR1 XVP 850-1800 Fig�31 AIR1 XVP 2500-3500 Fig�32 Main switch Outside air pre-filter (ePM10 50% /optional) Exhaust air Extract air filter (ePM10 50%) Outside air Warm water/electrical auxiliary heater (optional) Extract air Bypass damper Supply air...
  • Page 111 Installation and Operating Instructions Central ventilation units AIR1 XVP 3�3 Dimensions AIR1-XVP 850- 1800 Fig�33 ø32 ODA - Outdoor Air / Außenluft / Air extérieur EHA - Exhaust Air / Fortluft /Air rejeté ETA - Extract Air / Abluft / Air repris SUP - Supply Air / Zuluft / Air soufflé...
  • Page 112 Installation and Operating Instructions Central ventilation units AIR1 XVP 3�4 Performance curves AIR1-XVP 850 AIR1-XVP 1250 Δp Δp V · (m³/h) V · (m³/h) 1000 1200 1400 750 1000 1250 1500 1750 2000 AIR1-XVP 1800 AIR1-XVP 2500 Δp Δp 1200 1000 V ·...
  • Page 113 Installation and Operating Instructions Central ventilation units AIR1 XVP After selecting manual operation mode, the ventilation unit will run with the adjusted setpoints for the respective stage. Danger to life due to electric shock! DANGER An electric shock can result in death or serious injury� The unit is still live after selecting “Off”...
  • Page 114 Installation and Operating Instructions Central ventilation units AIR1 XVP Timer priorities (highest priority first): • Timer Boost • Timer Normal or VOD (higher ventilation requirement) • Timer Reduced • Timer Recirculation If the set timer times overlap, e.g. if the “Boost” timer and the “Normal” timer are programmed for the same time, the timer with the higher priority will be activated and the ventilation unit will be operated at the “Boost”...
  • Page 115 Installation and Operating Instructions Central ventilation units AIR1 XVP ration will not stop due to a high sensor requirement. → Timer VOD Timer recirculation Holiday Overrun ↑ Timer VOD Monday Per 1: XX:XX – XX:XX Per 2: XX:XX – XX:XX ↓...
  • Page 116 Installation and Operating Instructions Central ventilation units AIR1 XVP Adjustment of overrun time: • Log on as User or Admin • Call up the “Timer” menu • Call up the “Overrun” menu • Set the desired overrun time Overrun XXX min Time in overrun XXX min 4�1�6 Additional operating settings...
  • Page 117 Installation and Operating Instructions Central ventilation units AIR1 XVP • At an exhaust air temperature > 4°C, the heat exchanger frost protection is deactivated and the unit runs into normal operation. • If the preheater runs for more than 5 minutes at a power of 100 %, the ventilation unit goes into stand-by mode (out- side dampers close) and an alarm message appears, which must be reset manually to restart the unit.
  • Page 118 5 minutes from the last press of a button. All passwords can be modified in the “Access rights” menu under “Change password”. If the Admin password was modified and then forgotten, a temporary master password can be requested from Helios (Helios customer services).
  • Page 119 Installation and Operating Instructions Central ventilation units AIR1 XVP Main menu Helios Ventilatoren Programm vent.system AIR1 XVP 850 EXOreal C Version Choose Language 2023-06-22 09:30 Cross Counter Flow U Version: 3.7-0-51 3.5-1-04 German System: stopped 2023-04-16 SVN Build 4�5 Menu overview AIR1-BE Eco Main menu SP: 20.0 Act: 0.0°C...
  • Page 120 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of the main menu (Part 2 of 2) 7. Inputs / Outputs 9. Settings AI1: 0.0 Not used Control temp Supply air control AI exp3 AI2: 45.5 Humidity Control flow P-band: 33.0 °C AI exp4 AI3: 0.0 Not used...
  • Page 121 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 1 of 4) System Communication Recirculation Choose Language Expansion unit1 Enable temp Constant or function port1 English None control when setpoint offset Exp and freq/press Expansion unit2 recirculation when recirculation: None...
  • Page 122 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 2 of 4) Inputs / Outputs Sensor settings AI1: SAF pressure at AI1... AI exp3 Sign: Not used 0.0V: 0.0 AI exp4 Raw value: NaN 10.0V: 500.0 Pa Comepnsation: 0.0 Filter factor: 0.2 Pressure A exp3...
  • Page 123 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 3 of 4) Fire function Free cooling Pump control Fire damper function: Free cool P1 heating Pump stop: Yes Not active active: Yes P1 exchanger Stop delay: 1 Min Operation when alarm Outd temp activation P1 cooling...
  • Page 124 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 4 of 4) Step controllers Alarm settings Other parameters Step contr heating Step contr heating Start step1: 10 % Alarm no(1-125): 1 Malfunction supply a Delay SAF Step contr cooling Sequential Stop step1: 5 %...
  • Page 125 Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 5 5�1 Service and maintenance SERVICE AND The filter change is usually carried out by the user. Additional cleaning and maintenance work may only be carried out MAINTENANCE by an electrician. Danger to life! due to electric shock! DANGER The unit must be fully isolated from the mains power supply before all maintenance and installation work and...
  • Page 126 Installation and Operating Instructions Central ventilation units AIR1 XVP 5�3 Service and maintenance of cross counterflow heat exchanger Danger to life! The unit must be fully isolated from the mains power supply before all maintenance and installation work and DANGER opening the terminal compartment! Danger of electric shock, moving parts (fan) and hot surfaces�...
  • Page 127 Installation and Operating Instructions Central ventilation units AIR1 XVP 3. Carefully remove the profile (see Fig.39). Fig�39 4. Disassemble the cross-counterflow heat exchanger (see Fig.40). Fig�40 5. Remove the dampers (see Fig.41). Fig�41 5�3�2 Cleaning of cross-counterflow heat exchanger The cross counterflow heat exchanger must be regularly checked for dirt and dust deposits. The cross counterflow heat exchanger must also be checked for damage every 6 months.
  • Page 128 Installation and Operating Instructions Central ventilation units AIR1 XVP The technical data for the standard filter can be found in the table below: Filter Nominal air Number Filter class Dimensions Recommen- volume flow of filters (LxHxW) (mm) ded final (m³/h) pressure diffe- rential (Pa) AIR1 XVP 850 extr.
  • Page 129 Installation and Operating Instructions Central ventilation units AIR1 XVP The fan must be checked for contamination, damage and corrosion every 6 months: – Regular inspection with periodic cleaning, if required, is necessary to prevent imbalance due to contamination. – Clean the fans housing. –...
  • Page 130 Installation and Operating Instructions Central ventilation units AIR1 XVP 2. Clean the condensate tray with a cloth (see Fig.48). Fig�48 5�7 Cleaning the housing Danger to life due to electric shock! DANGER The unit must be fully isolated from the mains power supply before all maintenance and cleaning work. Risk of injury due to electric shock, moving parts (fan) and hot surfaces�...
  • Page 131 Installation and Operating Instructions Central ventilation units AIR1 XVP h� Functions Outside air damper • Auto = The outside air damper is automatically opened and closed by the controller, like during normal ventilation unit operation. • Close = The outside air damper is not activated and closes via a spring return. •...
  • Page 132 Installation and Operating Instructions Central ventilation units AIR1 XVP Alarm Priority Stop Check/Solution Filter change Filter guard 1 • Replace supply air filter Filter guard 2 • Replace exhaust air filter Temperature alarms Supply air control error • TARGET/ACTUAL temp. difference is greater than 5 K for 30 minutes •...
  • Page 133 Installation and Operating Instructions Central ventilation units AIR1 XVP Alarm Priority Stop Check/Solution Manual operation extract air fan • Control via operating mode manually mode Manual extract air fan frequency • Control via operating mode manually control Manual operation heater control •...
  • Page 134 Installation and Operating Instructions Central ventilation units AIR1 XVP Alarm Priority Stop Check/Solution Warning frequency converter EAF • Cause dependent on motor type. Contact service team Communication errors expansion units Communication error expansion • Communication with pressure sensor supply air fan inter- unit 3 rupted •...
  • Page 135 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1/KWL-VOC 0-10V Mixed gas sensor 20250 AIR1-CO2 K CO2 duct sensor 07124 AIR1-KP Condensate pump 06867 WHSH-HE 24 V (0-10 V) Hydraulic unit 08318 Accessory (AIR1-XVP 850) Ref� no� ELF-AIR1 XVP 850/ePM10 50%/48 Outside air pre-filter 40515 ELF-AIR1 XVP 850/ePM11 80%/96...
  • Page 136 Installation and Operating Instructions Central ventilation units AIR1 XVP Accessory (AIR1-XVP 2500) Ref� no� AIR1-JVK XC 2200/XVP 2500 Multi-leaf damper 06000 Accessory (AIR1-XVP 3500) Ref� no� ELF-AIR1 XVP 3500/ePM10 50%/48 Outside air pre-filter 40531 Outside air filter 40533 ELF-AIR1 XVP 3500/ePM11 80%/96 AIR1-EVH XVP 3500 Electrical preheater (contactor) 40507...
  • Page 137 Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 6 DECLARATION OF CONFORMITY...
  • Page 138 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP FRANÇAIS SOMMAIRE CHAPITRE 1 INFORMATIONS GÉNÉRALES ��������������������������������������������������������������������������������������������������������� PAGE 2 Informations importantes ........................Page 2 Précautions et consignes de sécurité ...................... Page 2 Demande de garantie – Réserves du constructeur .................. Page 2 Règlementations –...
  • Page 139 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP CHAPITRE 3 DONNÉES TECHNIQUES ������������������������������������������������������������������������������������������������������������� PAGE 39 Performances et données techniques ....................Page 39 Vue de l’appareil ..........................Page 40 Dimensions ............................Page 41 Courbes de performance ........................Page 42 CHAPITRE 4 DONNÉES TECHNIQUES �������������������������������������������������������������������������������������������������������������...
  • Page 140 Règlementations – Normes Sous réserve d’une installation correcte et d’une utilisation appropriée, cet appareil est conforme aux directives CE en vigueur au moment de sa fabrication. Les centrales AIR1 XVP.. d’Helios sont conformes à la directive ErP 2018 (directive sur l’écoconception) en vigueur.
  • Page 141 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Ces appareils ne sont pas destinés à être installés dans des locaux accessibles au public. Les restrictions d’utilisation des centrales AIR1 XH sont présentées dans le tableau suivant :: AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP...
  • Page 142 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Protéger avec un emballage sec, étanche à l’air et à la poussière (sac en matière synthétique contenant des sachets déshydrateurs et un indicateur d’humidité). Stocker le matériel dans un endroit à l’abri de la pluie, exempt de vibrations et de variations de températures excessives (plage de température ambiante : 0 °C min.
  • Page 143 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Si l’appareil est transporté à l’aide d’une grue, utiliser les trous sur le socle du châssis de transport (voir Fig.3). – Introduire la tringle de transport dans les trous du socle. –...
  • Page 144 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2�3�1 Mise au rebut Danger de mort par choc électrique ! DANGER Un choc électrique peut causer la mort ou de graves blessures. – S’assurer que l’appareil est hors tension et isolé. Mettre l’appareil à la terre, le court-circuiter et protéger les compo- sants adjacents sous tension.
  • Page 145 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP A: Distance minimale pour la maintenance au-dessus de l'appareil B: Profondeur de l’appareil C: Distance minimale pour l’ouverture devant l'appareil D: Hauteur de l’appareil (avec le boîtier électrique) Fig�4 Type Dimensions (mm) A (mm) B (mm) C (mm) D (mm)
  • Page 146 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Le bouchon de condensat doit être retiré avant la mise en service ! POINT IMPORTANT Un siphon à boule est disponible en tant qu’accessoire. REMARQUE 1. Le conduit des condensats est représenté ci-dessous (voir Fig.6). Fig�6 2.
  • Page 147 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 4. Déverrouiller les portes avec la clé fournie et ouvrir les portes (voir Fig.9). Fig�9 5. Retirer le bouchon de condensat à l’aide d’un tournevis (voir Fig.10). Fig�10 6. Dévisser le bouchon de condensat de la vis et serrer la vis à l’aide d’un tournevis (voir Fig.11). Fig�11 2�7 Raccordement des conduits sur la centrale...
  • Page 148 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Fig�14 Type Dimensions (mm) AIR1 XVP 2500 520 AIR1 XVP 3500 720 n : nombre de trous Dimension des trous / vis : M8 x16 – Visser le conduit, le raccord mixte et le raccord flexible du conduit dans les coins de l’appareil avec des vis M8x16 REMARQUE (AIR1 XVP 2500/3500).
  • Page 149 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 3. Insérer le filtre et le verrouiller comme indiqué ci-dessous (voir Fig.17). POINT IMPORTANT La classe de filtre doit être définie dans l’assistant de mise en service (voir chap. 2.11). Fig�17 2�9 Raccordement électrique...
  • Page 150 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2�9�1 Connexions électriques internes Les connexions électriques internes sont sécurisées par des clips de verrouillage, enlevez le clips de verrouillage avant le démonter le raccordement, voir Fig.18. Fig�18 2�9�2 Fixation de l’interrupteur principal L’interrupteur principal fait partie de la livraison et est joint à...
  • Page 151 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 3. Ouvrir le boîtier de l’interrupteur principal (voir Fig.22). Vérifier la section du câble utilisé pour le raccordement élec- trique. Fig�22 4. Desserrer le presse-étoupe et insérer le câble (câble d'alimentation et câble reliant l'interrupteur principal au boîtier de raccordement électrique dans l'appareil).
  • Page 152 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2. Ouvrir le couvercle du coffret électrique (voir Fig.26a). 3. Vérifier la section du câble utilisé pour le raccordement électrique. 4. Introduire le câble d’alimentation dans l’appareil (voir Fig.26b, c). Fig�26 ...
  • Page 153 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 4. Connecter l’autre extrémité du câble à la commande à distance (voir schéma de raccordement). Fig�30 AIR1 BE-ECO AIR1 BE-TOUCH 2 2�9�5 Modbus / Bacnet Les centrales AIR1 XH disposent d’une liaison RS-485 et d’une liaison Ethernet. La liaison RS-485 est utilisée pour la communication interne des sondes de pression.
  • Page 154 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 850 2�10 Schémas de raccordement Schéma de raccorde- ment principal SS-1506...
  • Page 155 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 850 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1516...
  • Page 156 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1250 Schéma de raccorde- ment principal SS-1507...
  • Page 157 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1250 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1517...
  • Page 158 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1250 Préchauffage électrique SS-1518...
  • Page 159 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1800 Schéma de raccorde- ment principal SS-1508...
  • Page 160 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1800 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1519...
  • Page 161 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 2500 Schéma de raccorde- ment principal SS-1509...
  • Page 162 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 2500 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1520...
  • Page 163 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 3500 Schéma de raccorde- ment principal SS-1510...
  • Page 164 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 3500 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1521...
  • Page 165 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2�11 Assistant de mise en service (« wizard ») Les principaux réglages de la centrale peuvent être effectués à l’aide de l’assistant de mise en service (à l’exception Assistant de mise en service du paramétrage, du mode d’urgence, de l’heure / la date et de l’horloge).
  • Page 166 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2�11�2 Activation du menu de l’assistant de mise en service (« wizard ») Étape 1 : se connecter en tant qu’administrateur (droits d’accès) ↑ Régulation du ventilateur Horloge → Droits d’accès ↓ → Connexion Déconnexion Modification du code Connexion...
  • Page 167 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Seule une centrale peut être sélectionnée. Le mot « aucun » s’affiche automatiquement dans les deux autres groupes. Le dernier réglage est valable. AIR1 XVP série Choisir configuration Aucune ↓ Choisir l'appareil de ventilation. Exemple: ↑...
  • Page 168 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP La valeur de consigne de la température de l’air soufflé est compensée en fonction de la température extérieure à l’aide d’une courbe de régulation à 8 points. Exemple : Température de l’air Température de l’air extérieur [°C] soufflé...
  • Page 169 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP e� Basculement entre régulation de l’air ambiant et air soufflé en fonction de la température extérieure REMARQUE Possible uniquement avec la sonde d’hygrométrie et de température AIR1/KWL-FTF 0-10V disponible en tant qu’ac- cessoire.
  • Page 170 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Température de l’air La température ambiante extérieur [°C] [°C] - 20 - 15 - 10 - 5 Mode de régulation de la tem- ↑ pérature Température ambiante en ↓ fonction de l’air extérieur ↑...
  • Page 171 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2�11�7 Mode de ventilation Le mode de ventilation est paramétré lors de la mise en service. Par la suite, ces paramètres peuvent uniquement être modifiés dans l’assistant de mise en service (niveau administrateur). Les modes de ventilation suivants sont disponibles : •...
  • Page 172 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP c� Pression constante Possible uniquement avec la sonde de pression AIR1-CAP disponible en tant qu’accessoire. Il peut être installé dans la REMARQUE gaine d’air soufflé ou dans la gaine d’air extrait. Un niveau de ventilation est disponible : •...
  • Page 173 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2�11�11 Type de chauffage Sélection des types de post chauffages disponibles. Les options suivantes sont disponibles : • Aucun • Eau (batterie eau chaude) • Électrique (batterie électrique) • DX batterie de chauffe (batterie à détente directe réversible DX) Appuyer sur la touche pour accéder au menu Type de chauffage.
  • Page 174 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Cette fonction est utilisée pour bloquer la fonction de chauffage après la surventilation pendant la période définie. Appuyer sur la touche puis procéder au réglage avec la touche . Confirmer avec la touche Sonde d’air extérieur ↑...
  • Page 175 Normal fermé 2�13 Paramétrage Le paramétrage s’effectue dans le menu principal après l’achèvement de l’assistant de mise en service. Il s’effectue via le sous-menu Régulation du ventilateur. Helios Ventilateurs 2019-XX-XX 09:30 Système : éteint Valeur de consigne : 19,5 Valeur réelle : 0.0 °C Mode de fonctionnement Température...
  • Page 176 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP En fonction du mode de fonctionnement sélectionné (débit d’air constant, pression constante, vitesse constante), les réglages suivants doivent être effectués : a� Débit d’air constant • Régulation du débit d’air du ventilateur de soufflage •...
  • Page 177 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP CHAPITRE 3 3�1 Performances et données techniques DONNÉES TECHNIQUES Les liaisons mécaniques doivent être réalisées correctement pour atteindre l’efficacité maximale de l’appareil. L’effica- cité thermique, le niveau sonore et la puissance électrique de l’appareil peuvent varier en fonction de l’environnement dans lequel il fonctionne.
  • Page 178 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 3�2 Vue de l’appareil AIR1 XVP 850-1800 Fig�31 AIR1 XVP 2500-3500 Fig�32 Interrupteur principal Préfiltre d'air extérieur (ePM10 50% /en option) Air rejeté Filtre d'air extrait (ePM10 50%) Air extérieur Batterie eau chaude/postchauffage électrique (en option) Air extrait Clapet de bypass...
  • Page 179 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 3�3 Dimensions AIR1-XVP 850- 1800 Fig�33 ø32 ODA - Outdoor Air / Außenluft / Air extérieur EHA - Exhaust Air / Fortluft /Air rejeté ETA - Extract Air / Abluft / Air repris SUP - Supply Air / Zuluft / Air soufflé...
  • Page 180 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 3�4 Courbes de performance AIR1-XVP 850 AIR1-XVP 1250 Δp Δp V · (m³/h) V · (m³/h) 1000 1200 1400 750 1000 1250 1500 1750 2000 AIR1-XVP 1800 AIR1-XVP 2500 Δp Δp 1200...
  • Page 181 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Selon le mode de commande manuelle choisi, la centrale fonctionne avec les valeurs de consigne définies pour le niveau sélectionné. m Danger de mort par choc électrique ! DANGER Un choc électrique peut causer la mort ou de graves blessures� L’appareil demeure sous tension y compris lorsque l’option Éteint est sélectionnée via l’unité...
  • Page 182 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Priorités du programme horaire (priorité la plus élevée en premier) : • Minuterie Boost • minuterie Normal ou VOD (besoin de ventilation plus élevé) • Minuterie Réduit • minuterie Régulation de la ventilation en recyclage Si les plages définies pour les programmes horaires se chevauchent (par ex.
  • Page 183 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Temps d’arrêt VOD : lorsque la centrale fonctionne pendant plus de 2 heures au niveau de ventilation Boost, la venti- lation pilotée par sonde est interrompue pendant le temps d’arrêt défini. Un nombre d’heures égal à 0 signifie que le pilotage par sonde ne s’arrête jamais en raison d’une forte sollicitation de la sonde.
  • Page 184 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP • accéder au menu programme horaire • accéder au menu Temporisation • Définir la durée de temporisation souhaitée Temporisation XXX min Durée de la temporisation XXX min 4�1�6 Autres réglages Les réglages suivants peuvent être effectués et les informations suivantes peuvent être consultées dans le menu princi- pal du dispositif de commande AIR1-BE Eco (voir le manuel dédié...
  • Page 185 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP • Dès que le préchauffage est commandé pendant plus de 3 minutes avec une puissance de 100 %, le débit total (air soufflé et air extrait) est réduit en permanence de max. 35 %. •...
  • Page 186 Si le mot de passe administrateur a été modifié puis oublié, un mot de passe maître temporaire peut être demandé au service après-vent d’Helios. Les menus ci-après sont uniquement consultables en lecture seule avec les niveaux utilisateur suivants (ou un niveau utilisateur supérieur)
  • Page 187 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Menu principal Helios Ventilatoren AIR1 XVP 850 Programm vent. syst. EXOreal C Version Choose Language 2023-06-22 09:30 Cross Counter Flow U Version: 3.7-0-51 3.5-1-04 Choisir la langue Système: Arrêté...
  • Page 188 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du menu principal (partie 2 de 2) 7. Entrées / Sorties 9. Réglages AI1: 0.0 Inutilisée Ctrl température Ctrl soufflage AI Ext3 AI2: 45.5 humides Ctrl débit Bande-P: 33.0 °C AI Ext4 AI3: 0.0 Inutilisée...
  • Page 189 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 1 de 4) Système Communication Recyclage Choose Language Unité d‘extension 1 Activer ctrl temp Consigne constante Fonction port1 Aucune quand recyclage ou décalage consigne Choisir la langue Ext et v.freq/press French...
  • Page 190 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 2 de 4) Entrées / Sorties Réglages sonde AI1: Pression VAS AI1... AI Ext3 Sign: Inutilisée 0.0V: 0.0 AI Ext4 Valeur mes: NaN 10.0V: 500.0 Pa Compensation: 0.0 Facteur filtre: 0.2 Pression A Ext3...
  • Page 191 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 3 de 4) Fonction incendie Surventilation Ctrl Pompes Fonction CCF: Surventilation P1-Chaud Arrêt pompe: Oui Inactif active: Oui P1-Échangeur Délai arrêt: 1 Min Opération si alarme: Temp ext activation: P1-Froid T °ext arrêt: 0°C...
  • Page 192 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 4 de 4) Séquenceur Config alarmes Autres paramètres Séquenceur chauff Séquenceur chauff: Marche étg1: 10 % Alarmes (1-125): 1 1. Défaut VAS Tempo VAS Séquenceur refroid Séquentiel Arrêt étg1: 5 %...
  • Page 193 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP CHAPITRE 5 5�1 Entretien et maintenance ENTRETIEN ET Il incombe généralement à l’utilisateur de procéder au remplacement des filtres. Les autres travaux de nettoyage et de MAINTENANCE maintenance doivent être effectués exclusivement par un électricien qualifié. Danger de mort par choc électrique ! DANGER Mettre impérativement l’appareil hors tension avant tous travaux d’entretien, d’installation et avant l’ouverture...
  • Page 194 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 5�3 Entretien et maintenance de l’échangeur à contre-courant Danger de mort ! Mettre impérativement l’appareil hors tension avant tous travaux d’entretien, d’installation et avant l’ouverture DANGER du boîtier électronique ! Risques de choc électrique, pièces mobiles (ventilateur) et surfaces chaudes� Risque de blessure ! AVERTISSEMENT Les échangeurs de chaleur pèsent lourd et peuvent contenir des condensats !
  • Page 195 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 3. Retirer soigneusement le profilé (voir Fig.39). Fig�39 4. Démonter l'échangeur à contre-courant (voir Fig.40). Fig�40 5. Retirer les volets (voir Fig.41). Fig�41 5�3�2 Nettoyage Il convient de contrôler régulièrement l’absence de saletés ou de dépôts de poussière au niveau de l’échangeur à contre-courant.
  • Page 196 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les données techniques des filtres standards sont indiquées dans le tableau suivant : Filtres Débit d’air Nombre Classe de filtre Dimensions Différence nominal (L x h x l) (mm) de pression (m3/h) filtres finale recom- mandée (Pa) Filtre d’air extrait AIR1 XVP 850 ePM10 50 %...
  • Page 197 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Vérifier l’absence de saleté, d’endommagement et de corrosion sur le ventilateur tous les 6 mois : – une inspection régulière et un nettoyage périodique sont nécessaires afin d’éviter tout déséquilibre lié à la saleté. –...
  • Page 198 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2. Nettoyer le bac à condensat avec un chiffon (voir Fig.48). Fig�48 5�7 Nettoyage du caisson Danger de mort par choc électrique ! DANGER Mettre impérativement l’appareil hors tension avant tous travaux d’entretien et de nettoyage. Risque de blessure par choc électrique, pièces mobiles (ventilateur) et surfaces chaudes�...
  • Page 199 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP g� Fonctions P1 batterie de refroidissement (pompe du groupe eau glacée) • Éteint = la pompe est éteinte. • Auto = la pompe est allumée et éteinte automatiquement par le régulateur comme lors du fonctionnement normal de la centrale.
  • Page 200 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Alarme Priorité Arrêt Vérification / Solution Commande externe VAR • Le ventilateur tourne malgré l’arrêt de l’installation • Vérifier les entrées externes • Le ventilateur est peut-être entraîné par le ventilateur de secours •...
  • Page 201 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Alarme Priorité Arrêt Vérification / Solution Alarmes en mode manuel Sortie en mode manuel • Vérifier les réglages dans le menu de configuration Ctrl Soufflage en mode manuel • Pilotage via le mode de commande manuelle Vas en mode manuel •...
  • Page 202 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Alarme Priorité Arrêt Vérification / Solution Erreur com. variateur frég. VAR • Le ventilateur d’extraction ne reçoit pas le signal Modbus • Vérifier le câblage de l’alimentation électrique • Vérifier le câblage Modbus entre le ventilateur et le disposi- tif de commande Alerte variateur frég.
  • Page 203 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP MEMO à compléter : paramètres saisis dans l'assistant de mise en service Langue Type de filtre Air neuf : Type de centrale : Commande externe : OUI / NON Type de filtre Air repris : Type de régulation de température : Type de batterie de post-chauffage : ELEC / EAU...
  • Page 204 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Accessoire (AIR1-XVP 1250) Ref� no� ELF-AIR1 XVP 1250/ePM10 50%/48 Préfiltre d'air extérieur 40519 ELF-AIR1 XVP 1250/ePM11 80%/96 Filtre d'air extérieur 40521 Préchauffage électrique AIR1-EVH XVP 1250-3,6 (protection) 40480 Préchauffage électrique AIR1-EVH XVP 1250-2,6 (protection) 40481...
  • Page 205 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Accessoire (AIR1-XVP 3500) Ref� no� AIR1-CO DX XVP 3500 L Batterie à détente directe réversible 40512 AIR1-CO DX XVP 3500 R Batterie à détente directe réversible 40513 AIR1-ÜS XC 3200/XVP 3500 Pièce de transformation rond-carrée 04365 AIR1-VS 70/40...
  • Page 206 EU Declaration of Conformity to EC Machinery Directive 2006/42/EC Annex II Part 1A / Déclaration de conformité UE selon la Directive CE relative aux machines 2006/42 Note II Partie 1A Helios Ventilatoren GmbH + Co KG Lupfenstr. 8, D-78056 Villingen-Schwenningen Hiermit erklären wir, dass die Produkte in Übereinstimmung mit den untenstehenden Richtlinien entwickelt,...