11. Technical specifications
Input data:
Measuring ranges
Overload pressures
EN
Burst pressure
Mechanical connection
Torque value
Parts in contact with medium
Output data:
Accuracy to DIN 16086,
max. setting
(Display, Analogue output)
Repeatability:
Temperature drift EDS 1700-P
Temperature drift EDS 1700-N
Analogue output:
Signal (selectable)
Switching outputs*:
Type
Switching voltage
Switching current
Switching output
Switching cycles
Reaction time
Ambient conditions:
Compensated temp. range
Operating temperature range
Storage temperature range
Fluid temperature range
mark
Vibration resistance to
DIN EN 60068-2-6 (0 .. 500 Hz)
Shock resistance to
DIN EN 60068-2-29 (1 ms)
Protection class to IEC 60529
34
16; 40; 100; 250; 400; 600 bar
32; 80; 200; 500; 800; 1000 bar
200; 200; 500; 1000; 2000; 2000 bar
Threaded port G1/4 DIN 3852
20 Nm
Mech. connection: Stainless steel
EDS 1700-P: ≤ ±0.5 % FS max.
EDS 1700-N: ≤ ±1.0 % FS max.
EDS 1700-P: ≤ ±0.25 % FS max.
EDS 1700-N: ≤ ±0.5 % FS max.
≤ ± 0.02 % FS / °C max. zero point & range
≤ ± 0.03 % FS / °C max. zero point & range
4 .. 20 mA, ohmic resistance ≤ 400 Ω
0 .. 10 V, ohmic resistance ≥ 2 kΩ
4 relays with change-over contacts in 2 groups
(common supply of each group connected)
0.1 .. 250 V AC, 12 .. 32 V DC
0.009 .. 2 A per switching output
max. 50 W / 400 VA
(for inductive load, use varistors)
20 million min. load
1 million max. load
approx. 20 ms
-10 .. + 70 °C
-25 .. +60 °C
-40 .. +80 °C
-25 .. +80 °C
EN 61000-6-1, EN 61000-6-2,
EN 61000-6-3, EN 61000-6-4
≤ 5 g
≤ 10 g
IP 65