NTP PoE model with battery:
In the case of mains failure, the lighting (if this option has been selected) goes off. All the hands
continue to work since power is supplied to the card by the PoE network. If the PoE network is also
cut off, the second hand stops at noon but the hour and minute hands continue to operate for an
hour, powered by the battery. After an hour, all the hands stop moving. They are set at noon when
the PoE power supply is restored. Then, the clock resynchronises itself and the lighting comes back
on when the mains power supply is restored.
The full factory configuration is as follows:
- Clock name: "BODET-@MAC".
- IP configuration by DHCP.
- Time zone: EUR.
- Synchronisation: Multicast (239.192.54.1).
- Trap type: V2C.
- Pool period for unicast synchronisation: 15 min.
- SNMP disabled.
- No password.
- Trap status issue period: 24H.