Switching status of the outputs
Output function
[Fno]
[Fnc]
Both window limit values ([nPx] and [FPx]) work with a switching hysteresis
→ 10.2.4 Hysteresis functionexample for output function [Hno].
10.2.9 Setting of the switch points for window function OUT1 / OUT 2
► Change to [EF]�
► In [OU1] select the output function [Fno] or [Fnc]�
► Confirm with [ENTER]�
► Select [nP1] and set the switch point "near"�
► Confirm with [ENTER]�
► Select [FP1] and set the switch point "far"�
► Confirm with [ENTER]�
10.2.10 Teach - Setting of the switch point for window function OUT1 / OUT2
► Change to [EF]�
► In [OU1] select the output function [Fno] or [Fnc]�
► Confirm with [ENTER]�
► Change to [EF] and select [tn1]�
> Parameter value for [nP1] is displayed�
► Press the "up" or "down" button and keep it pressed�
> The parameter value flashes for 3 s�
> New parameter value is displayed�
► Confirm with [ENTER]�
► Change to [EF] and select [tF1]�
> Parameter value for [FP1] is displayed�
► Press the "up" or "down" button and keep it pressed�
> The parameter value flashes for 3 s�
> New parameter value is displayed�
► Confirm with [ENTER]�
Object distance (D)
D < [nPx]
D > [FPx]
[nPx] < D < [FPx]
D < [nPx]
D > [FPx]
[nPx] < D < [FPx]
Switching status
Open
Closed
Closed
Open
0v1
0v2
np1
fp1
0v1
0v2
tn1
tf1
np1
fp1