► Keep the "up" + "down" button pressed until
[uLo] is displayed�
> The unit is unlocked�
Timeout
If no button is pressed for 15 s during the setting procedure, the unit returns to the
run mode with unchanged values�
10.2 Configuration of the basic settings
10.2.1 Selection of the display unit
Set [Uni] before the values for the parameters [SPx], [nPx], [FPx] are
defined�
In case of subsequent changes of the display unit rounding errors during
internal conversion to other units may falsify the set values�
► Change to [EF]�
► Select [Uni] and set the unit of measurement�
Selection of the unit of measurement: [mm], [Inch]
► Confirm with [ENTER]�
> The selected unit is indicated by a green LED on the display�
10.2.2 Setting the display
► Change to [EF]�
► Select [diS] and make settings�
2 settings can be selected:
• [On] = the measured value display is activated in the run mode�
• [OFF] = the measured value display is deactivated in the run mode�
When one of the buttons is pressed, the current measured value is
displayed for 15 s�
► Confirm with [ENTER]�
The LEDs remain active even if the display is deactivated�
10.2.3 Configure OUT1 / OUT2
► Select [OU1] / [OU2] and set the switching functions�
Switching functions:
• [Hno] = hysteresis function / normally open
• [Hnc] = hysteresis function / normally closed
• [Fno] = window function / normally open
• [Fnc] = window function / normally closed
• [OFF] = switching output is deactivated
► Confirm with [ENTER]�
UK
vni
di5
0v1
0v2
45