Faulty states on start-up
I messaggi di errore sotto indicano un'anomalia presente al
momento della messa in funzione dell'impianto:
SIGNAL
DESCRIPTION
E1
Flashing
Door parameters acquisition fail error,
proceed with procedure
E5
Flashing
Main key not inserted or not configured
error
E6
Flashing
Supervised sensors acquisition fail error,
proceed with procedure
E1
E6
To resolve errors
and
, follow the procedures described in
the manual in the Learn Parameters and Learn Sensors section. For
E5
error
, check that the main key is inserted correctly or replace
the main key with one that works.
SIGNAL
DESCRIPTION
E7
Flashing
Safety function intervention error see
subsequent detail
E8
Flashing
Motor or encoder connection error, check
wiring
E9
Flashing
Communication error with Safety
Controller during the movement of the
door
E7
The code
indicates a persistent fault in the internal safety
circuit of the control unit that leads to the door being stopped
for safety reasons. The code flashes alternating with the numeric
code in the table below which indicates the source of the problem
SIGNAL
DESCRIPTION
-2
Flashing
Communication error with User controller
-3
Flashing
No inversion error following Safe Close
activation
-4
Flashing
No stop error following Safe Open
activation
-5
Flashing
Motor control overload error
-6
Flashing
Motor control watchdog error
-7
Flashing
Safety function data management CRC
error
If the problem persists, replace the control unit.
E9
indicates a permanent error generated by the temporary cause
F8
. If the problem persists, replace the control unit.