31 - CONTROL UNIT AND SENSORS
COMPLIANT WITH EN16005
Fig.10 outlines the sensors which can be connected to the control
unit:
A - left safety sensor in opening
B - internal safety sensor in opening
C - external safety sensor in opening
D - right safety sensor in opening
The opening sensors B and C perform the following 3 functions:
1. opening command: detects movement in zone M1 or M2 and
controls opening of the doors
2. safety in closure: detects the presence in zone A1 or A2 and in
the event of an obstacle prevents closure of the doors
3. test: check safety in closure (function 2) is working properly; in
the event of a fault, they prevent door closure (ref. EN16005
performance level C)
SENSOR
A
B
C
D
NOTE: for more detailed information on cable colours and terminal boards, refer to the specific manual supplied with the sensor relating to
the model chosen.
m
DANGER: choose and install the sensors based on the architectural formation of the entrance based on careful risk
analysis in compliance with EN16005. On the contrary, automatic movement of the doors could cause serious damage to
property and people with the risk of fatal injuries.
All manuals and user guides at all-guides.com
FUNCTION
Power
1. (Opening safety)
2. (Test)
Power
1. (Opening command)
2. (Closure safety)
3. (test)
Power
1. (Opening command)
2. (Closure safety)
3. (test)
Power
1. (Opening safety)
2. (Test)
The safety sensors A and D perform the following 2 functions:
1. safety in opening: detects the presence in zone A3 or A4 and
in the event of an obstacle prevents opening of the doors
2. test: check safety in opening (function 1) is working properly;
in the event of a fault, they prevent door opening (ref.
EN16005 performance level C)
The following table outlines the connections of sensors A, B, C, D
with the control unit terminals.
The 2 power function cables are the power supply cables.
The default column outlines the factory setting values of the
contacts (NO/NC):
TERMINAL BOARD (Fig.68)
19 (-)
20 (+)
16
17
14
15
6 (-)
7 (+)
2
5
10
13
8
9
6 (-)
7 (+)
1
2
10
12
8
9
19 (-)
20 (+)
16
18
14
- 32 -
DEFAULT
NC
NO
NO
NC
NO
NO
NC
NO
NC
NO