33 - AUTOMATISM START-UP
To prepare the automated system for use, follow the sequence below:
1. connection of battery and network power supply (230Vac);
LS
2. Learn Sensors (
) procedure
LP
3. Learn Parameters (
) procedure;
4. adjustment of parameters if necessary;
5. checks of screws, anti-derailing carriages, case and all elements subjected to vibrations during operation;
6. final test of the correct function of all safety devices installed with the use of specific instrumentation prescribed by EN16005;
m
DANGER: each of the activities 1 to 6 listed above are fundamental to the safety of the system; ensure the person
responsible is suitably qualified and do not skip any steps or checks. Otherwise an important safety function may be disabled
and the automatic movement of the doors may cause serious injury or damage to persons or objects, risking potentially fatal
lesions.
m
WARNING: if there is no optional device for controlling the door at night, ensure the KEY input is short-circuited with
the COM input (terminals 22 and 23); otherwise it will not be possible to activate the automated system; if there is no sensor
compliant with EN13849-1 performance level "d" installed in the terminals 3-4, short-circuit between the two terminals;
otherwise it will not be possible to activate the automated system.
In the presence of the electric lock, follow the table:
ID
DESCRIPTION
13
Type of electric
lock
30
Test Safe Close
output polarity
In the presence of batteries, follow the table:
ID
DESCRIPTION
33
Battery
management
All manuals and user guides at all-guides.com
ADJUSTMENT
0 Not used
1 Normal
2 Inverse
3 Bistable
4 Bistable safety with door lock only using a motor if the KEY is active
0 NA
1 NC
ADJUSTMENT
0 Battery not used
1 Battery present - normal operation
2 Battery present - anti-panic operation
3 Battery present - safety operation and control of battery capacity
- 34 -
VALUE TO SET
1
1
VALUE TO SET
1