2. Troubleshooting
Heater Will Not Fire - B
Start
Is red "SERVICE
HEATER" LED "on"
YES
CONTINUE
P/N 475106 Rev. D 1/2016
All manuals and user guides at all-guides.com
NO
Is red "SERVICE SYSTEM"
LED on?
Verify that pump is on, filter is
not blocked, and the water
flow is above the minimum
requirement.
With pump running, adjust
Water Pressure Switch to
lower pressure until 'SER-
VICE SYSTEM" LED goes
out. Then verify that "SER-
VICE SYSTEM" LED goes on
with pump off.
Check that water pressure is
within the adjustment range of
the Pressure Switch (0-35 kPa).
Verify that switch wiring is OK
and Pressure Switch port is
not blocked, and replace
water Pressure Switch.
Check whether any of the
red diagnostic LED's on back
of board (AGS, AFS, SFS,
HLS or PS) are "on"
GO TO
"HEATER WILL NOT FIRE - C"
Page 28
NO
YES
NO
YES
YES
NO
NO
YES
YES
NO
™
MASTERTEMP
Pool and Spa Heater Installation and User's Guide
Increase POOL/SPA tempera-
ture setting on Membrane
Pad above actual water tem-
perature. Heater should fire
on demand for heat. If not,
and no other red LED's light,
replace Control Board.
Service pump/filter and elimi-
nate other flow obstructions.
Heater should fire on call for
heat. Re-verify that water flow
is above minimum require-
ment.
Minimum Flow Requirements
Model
Flow
200HD
160 LPM
300HD
200 LPM
400HD
240 LPM
If water pressure is outside of
adjustment range that will
open switch with pump off
and close switch with pump
on, replace with flow switch
set above minimum flow
requirement.
Minimum Flow Requirements
Model
Flow
200HD
160 LPM
300HD
200 LPM
400HD
240 LPM
Go to "Diagnostic LED's",
(Pages 30 and 31)
| 27