6 | Section
1. Operations
SAFETY CONTROLS,
OPERATION OF IGNITION MODULE
, (see Figure 5),
The Ignition Module
operates on 24VAC supplied by the transformer. The control utilizes
a microprocessor to continually and safely monitor, analyze, and
control the proper operation of the gas flame holder. The module
with the presence of the flame sensor, using flame rectification,
allows the heater to operate.
TEMPERATURE SETTING
The heater comes factory set at 25.6° C (78° F). for the pool mode and 37.8° C (100° F). for the spa mode. Using the up
and down arrows, you can set the pool/spa thermostats to a minimum temperature of 18.3° C (65° F.), or a maximum of
40° C (104° F). If you desire to heat only one body of water, the thermostat is capable of an off mode. As an example, if
you only wish to heat the spa and not the pool, simply depress and hold the pool down arrow, and the thermostat will
lower its setting to 18.3° C (65° F.) then go to an off mode. See below to change the heater's factory set temperature
settings.
MAXIMUM TEMPERATURE SET POINT
1. Unbolt and remove the door panels (see Figure 6).
2. Access the control panel board on the underside of the top cover.
Locate the yellow button on the corner of the control board.
3. Push the Max. Temp. Set Point button on the back of the
control board (see Figure 7).
The following sequence should happen:
The unit turns on and the POOL ON light will
1.
turn on.
TEMP or TEMP
2.
Press the
control panel) to set maximum pool temperature.
Wait up to 30 seconds; the POOL ON light will turn off
3.
and the SPA ON light will turn on. To override the time
delay, push the Max. Temp. Set Point button again.
TEMP or TEMP
4.
Press the
panel and set maximum spa temperature to 40°C
(104° F) or less.
Wait up to 30 seconds; the SPA ON light will turn off
5.
and the unit will shut down. To override the time delay,
push the Max. Temp. Set Point button again.
6.
Reinstall the access door panels.
™
MASTERTEMP
Pool and Spa Heater Installation and User's Guide
All manuals and user guides at all-guides.com
(continued)
is microprocessor based and
button (on TOP of the
button on the control
Diagnostic LED
Flame Current
1 Flash
Check Point
2 Flashes - Flame No Call For Heat
3 Flashes - Ignition Lockout
Top Panel
Door
Access Panel
- Air Flow Fault
Figure 5.
Door
Access
Panel
Figure 6.
Figure 7.
P/N 475106 Rev. D 1/2016