3.3.10 Programming field 9 : select size of battery bank

This function enables to adjust BOOST trimming versus size of battery bank

3.3.11 Programming field 10 : select CAN protocol

This function enables to change CAN protocol

3.3.12 Thermal compensation

STP-UNI-2.8 and STP-UNI-5.0 temperature probes enable the compensation of Absorption voltage and Floating Voltage
depending on the ambient temperature of the battery room.
The coefficient used is -18mV/°C for 12V model and -36mV/°C for 24V models.
Temperature is not compensated when wintering (or standby sealed bat),
stabilized DC power supply and lithium iron phosphate (LiFePO4)
with BMS settings are selected.
Option not compatible with option alternator protection.

3.3.13 Alternator protection

STP-ALT-2.4 temperature probes enable the protection of the alternator
Option not compatible with option thermal compensation.
Setting
Factor of multiplication of BOOST trimming
1
2
3
4
5
Setting
1
2
3
4
1
1.5
2
2.5
3
CAN-Bus protocol
Protocol Cristec
Protocol SH
Protocol PH
Protocol J1939
from a
temperature too high.
41