HARGER FAULT RELAY
Two dry contacts are available, normaly open (NO) and normaly closed (NC).
The relay is deactivated if :
-
The charger is off ;
-
The charger is faulty ;
-
The output fuse is broken ;
-
The Charger voltage (before distribution) is below 11V ± 5% (for 12V models) or 22V ± 5% (for 24V
models) for more than 10 seconds. Hysteresis is approximately 0.5V.
2
R
BATTERY LOW
Two dry contacts are available, normaly open (NO) and normaly close (NC).
Monitoring is carried out on the output + BAT 1 only and is independent of the operation of the charger.
The relay when activacted, consumes about 12mA on the output + BAT 1.
The relay is activacted if the battery park voltage +BAT 1 is above 10.2V ± 5% (for 12V models) or 20.4V ±
5% (for 24V models). Hysteresis is approximately 1V.
3 A
NALOG VOLTMETER AND AMMETER CONNECTION
It's possible to connect voltmeters on outputs +BATE, +BAT1 and +BAT2 and a ammeter to read the load
current (excluding 12V-25A and 12V-16A models).