3.2.2. Cable from the public AC power supply network or generator
All CPS3 battery chargers can operate automatically on single phase networks from 85 to 265VCA and from 47 to
65Hz.
Generators:
The CRISTEC battery chargers are designed to operate from a generator.
Be careful:
In some cases, the generators can produce high over voltages, in particular during starting
phase. Before connecting the charger, please check its compatibility with the characteristics of the
generator: power, voltage, overvoltage, frequency, current... It's highly advised to disconnect the charger
from the AC network during the generator starting phase.
The power cable must be connected to screw terminal board K1 (PE, ACN and ACL terminals):
PE : Earth
ACN : Neutral
Depending on line lengths, the cross-section ofAC power cables must be at least equal to or greater than the values
provided in the table below:
Minimum cross-
Model
section for 115VAC
CPS3/12-80
CPS3/24-60
3 x 4 mm²
CPS3/24-75
CPS3/48-30
The PE conductor (commonly called earth , the green and yellow wire) of the AC source must be connected to the
charger on the terminal provided for the purpose, and this must be done before connecting any other terminals.
Please refer to the relevant diagram in the chapter "user interface area".
The rating of the upstream circuit-breakers should match the equipment's requirements.
Remarks:
The CPS3 chargers are working as soon as they are connected (connected and supplied AC network cable)
The CPS3 chargers are stopped as soon as they are not anymore under voltage (disconnected AC network cable or
circuit breaker of the installation in OFF position).
BE CAREFUL: if the ON/OFF charger accessory is used, the charger can be stopped but nevertheless still being
under voltage (dangerous voltage).
Power limiting switch
A switch on the outside of the case (the cable lead-in
side) limits the charger's output power (on position 1) :
This may prevent the differential circuit-breaker at the
beginning of the 230/115VAC line from tripping.
3.2.3. Battery cable
Please check imperatively the compatibility of voltage, current and setting according to the connected battery type
before switching ON the charger.
Check of the charge voltage
Before connecting the batteries to the charger, imperatively check the polarity of the batteries.
Equally check the battery voltage thanks to a calibrated voltmeter. A too lower voltage value on some types of
batteries can point out an irreversible damage of them and so an impossible recharge.
The CPS3 charger is equipped with 5 output terminals:
K4:
- BAT (minus set of batteries)
K5:
+BAT D (plus engine battery for marine-type applications)
K6:
+BAT 1 (plus battery set 1)
K7:
+BAT 2 (plus battery set 2)
K12 : +SP (external battery isolator input particular case)
Be careful: a direct connection of a battery on the SP terminal could destroy the charger,
imperatively connect a battery isolator between the battery and the SP terminal).
3 metres
Up to
, the cross-section of the battery cables should be at least equal to or greater than the values
provided in the table below:
CPS3-3M-DED
ACL : Phase
The type of cable (H07-VK, MX, etc.) should be
defined by the installer according to the application
Minimum cross-
type and the enforceable standards.
section for 230VCA
For applications where the electricity network may be
either 115VAC or 230VAC, always choose the cross-
section recommended for 115VAC.
3 x 2,5 mm²
Always use cable markers with insulating collars in
accordance with installation standards governing AC
network input connections.