Note the voltage and current type as specified on
the rating plate.
Tighten cable plug (for permitted types see data sheet),
observing max. torque 1 Nm.
Check that seal is fitted correctly.
Connect protective conductor and check electrical con-
tinuity between coil and housing.
7.7.1.
electrical connection - pulse
4
2
3
1
Fig. 9:
Circuit diagram
The connection terminals in the device socket are
identified with the numbers 1 to 3 according to the
terminals on the valve.
8.
mainTenance,
TrOubleshOOTing
8.1.
safety instructions
Danger!
Risk of injury from high pressure in the equipment!
Before loosening the pipes and valves, turn off the
pressure and vent the pipes.
Risk of injury due to electrical shock!
Before reaching into the device or the equipment,
off the power supply and secure to prevent reactivation!
Observe applicable accident prevention and safety
regulations for electrical equipment!
Warning!
Risk of injury from improper maintenance!
Maintenance may be carried out by authorized techni-
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
Secure system from unintentional activation.
Following maintenance, ensure a controlled restart.
DC connections:
Terminal 1 = closed +
Terminal 2 = open +
Terminal 3 = GND -
Protective conductor
connection
english
25
switch
english
27
Procedure:
Pulse valves (variable code CF 02) as in
connect.
For direct current versions connect negative terminal to
terminal 3.
note!
Important information:
Avoid emitting pulses simultaneously to both coil
windings.
Do not switch any other consumers (relays, etc.) at the
same time as the terminals.
The coil connection, to which voltage is not applied,
must be galvanically isolated (open).
If two or more valves are switched in parallel, ensure
that this requirement is met by using 2-pole or multi-
pole switches.
english
26
8.2.
malfunctions
If malfunctions occur, check whether:
the device has been installed according to the
instructions,
the electrical and fluid connections are correct,
the device is not damaged,
all screws have been tightened,
the voltage and pressure have been switched on,
the pipelines are clean.
Valve does not switch
Possible cause:
Short-circuit or coil interrupted.
Medium pressure outside the permitted pressure range.
Manual emergency actuation locked.
Valve does not close
Possible cause:
Internal space of the valve is dirty.
Manual emergency actuation locked.