6.4

Operating conditions

Observe permitted ranges on the type label of the
device!

6.4.1 Temperature ranges

The globe valve is suitable for steam sterilization.
Actuator
Actuator
size [mm]
material
50
70
PPS
90
130
Tab. 2:
Temperature ranges
1) If a pilot valve is used, the max. ambient temperature is +55
°C.
2) Pilot air ports with push-in connector
3) Pilot air ports with threaded bushing
8
Medium
Environment
(for PTFE seal)
-10 ... +60 °C
-10 ... +185 °C
-10 ... +100 °C
english

6.4.2 Pressure ranges

Actuator size [mm]
50
70
90
130
Tab. 3:
Pressure ranges
4)  F orthedeviceversionø70/Orifice50/MC13themax.
1)
permitted pilot pressure is limited to 7 bar.
Minimum pilot pressure: flow below the seat
(medium flow against the closing direction of the valve)
2)
Required minimum pilot pressure P
3)
Actuator
50
size [mm]
P
[bar]
5,2
min
The required minimum pilot pressure P
I (flow below the seat) is dependent on the pressure of the medium
Minimum pilot pressure: flow above the seat
(medium flow with the closing direction of the valve)
The required minimum pilot pressure P
A (flow above the seat) is dependent on the pressure of the
medium
.
5)
5) The pressure diagrams are in the operating instructions on
the Internet:
Type 2101
Technical data
Maximum pilot pressure
10 bar
7 bar
with control function A:
min
70
90
130
≤ DN 50
4,8
5,0
5,0
with control function B and
min
with control function
min
country.burkert.com
4)
130
≥ DN 65
5,6
.
5)

Publicité