Burkert 2101 Mode D'emploi page 12

Vanne à siège droit 2/2 voies
Masquer les pouces Voir aussi pour 2101:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

→ Screw actuator into the valve body.
Observe tightening torque "Tab. 1: Temperature ranges Ex
area").
Air discharge connection
CFA, CFB
Pilot air port CFI
Pilot air port
CFA, CFB, CFI
Fig. 4:
Pneumatic connection
DN
15
20
25
32
40
50
65
80
100
Tab. 5:
Tightening torque valve body / nipple
12
2
1
Tightening torque [Nm]
45 ± 3
50 ± 3
60 ± 3
65 ± 3
70 ± 3
100 ±3
120 ± 5
150 ± 5
english
Type 2101
Installation
7.3.3 Install control
Description see Installation chapter in the operating
instructions for the corresponding control.
7.3.4 Rotating the actuator
The position of the connections can be aligned steplessly by
rotating the actuator through 360°.
NOTE!
Damage to the seat seal or the seat contour.
▶ When rotating the actuator, ensure that the valve is in open
position.
Procedure:
→ Clamp the valve body in a holding device
(applies only to valves which have not yet been installed).
→ Control function A pressurize the pilot air port 1 with com-
pressed air (5 bar): valve opens.
→ Counter on the flats of the nipple with a suitable open-end
wrench.
→ Place suitable open-end wrench on the hexagon of the
actuator.
WARNING!
Risk of injury from discharge of medium and pressure.
If the direction of rotation is wrong, the body interface may
become detached.
▶ Rotate the actuator module in the specified direction only.

Publicité

Table des Matières
loading

Table des Matières