P1314 SENSOR RANGE
20mA - 10.00bar
Actual Value
Left fct.
Up fct.
Sets the end range value (20 mA or 10 V) of the
connected sensor. In particular, the end range value
(20 mA or 10 V) must be always equal to the 100%
of the sensor range (that is, for a 0.4 bar differential
pressure sensor, is 20 mA=0.4 bar).
P1315 REQUIRED VAL.
P1315 REQUIRED VAL.
XXXXX bar
Actual Value
Left fct.
Up fct.
The information shown on the display depend on the
selection done in parameter 1309: when parameter
P1309 MODE is set to Controller, Cascade Relay,
Cascade Serialor Cascade Synchron, display
shows REQUIRED VAL. as the parameter descrip-
tion. When parameter P1309 MODE is set to Actua-
tor, display shows ACTUAT.FRQ.1 as the parameter
description.
P1316 START VALUE
P1316 START VALUE
100 %
Actual Value
Left fct.
Up fct.
Sets the end range value (20 mA or 10 V) of the
connected sensor. In particular, the end range. This
parameter defines, in percentage (0-100%) of the re-
quired value (P1315 REQUIRED VAL.), the start val-
ue after pump stops.
If P1315 REQUIRED VAL. is met and there is no
more consumption, then the pump stops. The pump
starts again when the pressure drops below P04
START VALUE. Value 100% makes this parameter
not effective (100%=off)!
P1317 MIN.THRESH.
P1317 MIN.THRESH.
Disabled
Actual Value
Left fct.
Up fct.
Selects the minimum threshold limit: if an adjusted
value > 0.00 is not reached within the P1318 DE-
LAY-TIME, then the unit stops (failure message:
MIN.THRESH.ERROR).
P1318 DELAY-TIME
Output Freq.
Down fct.
Right fct.
Output Freq.
Down fct.
Right fct.
Output Freq.
Down fct.
Right fct.
Output Freq.
Down fct.
Right fct.
P1318 DELAY-TIME
2 sec
Actual Value
Left fct.
Up fct.
Selects the delay time of the minimum threshold lim-
it: it shuts off the HYDROVAR if the actual value
drops below P1317 MIN.THRESH. or if a low-water
protection (at terminals X1/16–17) becomes open.
P1319 DATE
P1319 DATE
XX.XX.20XX
Actual Value
Left fct.
Up fct.
Using this parameter current date can be set.
P1320 TIME
P1320 TIME
HH.MM
Actual Value
Left fct.
Up fct.
Using this parameter current time can be set.
P1321 AUTO-START
P1321 AUTO-START
ON
Actual Value
Left fct.
Up fct.
If AUTO-START = ON, then the HYDROVAR starts
automatically (in case of demand) after reconnection
of power following disconnection.
P1322 START-UP COMPLETED?
P1322 STARTUP COMPLETED?
No
Actual Value
Left fct.
Up fct.
If the user configured the whole application by se-
lecting "YES" then the HYDROVAR will not make
available the Start-up menu at every power-on.
By selecting "NO" at next power-on, the HYDRO-
VAR will offer to the user the start-up procedure.
P1323 ADDRESS
P1323 ADDRESS
Actual Value
Left fct.
Up fct.