6.2.
Operating conditions
6.2.1.
Temperature ranges
permitted ambient temperature actuators
actuator size
actuator material
ø 50 mm
ø 70 mm
PPS
ø 90 mm
If a pilot valve is used, the max. ambient temperature
1
is +55 °C
12
All manuals and user guides at all-guides.com
environment
1
0 – +60 °C
english
Type 2103
Technical Data
permitted medium temperature for housing
housing material
Cast housing (VG)
1.4435 (AISI 316L)
1.4435 BN2 (AISI 316L)
Forged housing
according to ASME BPE
(VS)
1997
permitted medium temperature for diaphragms
The indicated medium temperatures apply only to media
which do not corrode or swell the diaphragm materials.
The behaviour of the medium with respect to the dia-
phragm may be changed by the medium temperature.
The function properties, in particular the service life of the
diaphragm, may deteriorate if the medium temperature
increases.
diaphragm medium
EPDM
-10 – +130 °C
FKM
0 – +130 °C
PTFE
-10 – +130 °C
medium
-10 – +150 °C
remarks
Steam sterilisation: up to +150 °C
•
dry up to + 150 °C
•
otherwise only briefly up
to +150 °C
Steam sterilisation: up to +150 °C