5.5 Alarm configuration
This page is used to enable clock supervision, to define the information to be transmitted and the
destination server. One or more settings can be defined and configured as alarms.
The following information is displayed:
• Enable SNMP Trap: If enabled, error messages are sent to the SNMP Manager(s)
automatically.
• SNMP Manager 1/2/3: IP addresses of servers receiving alerts from the clocks.
SNMP Manager redundancy increases the reliability of alerts.
• Community: A set of clocks defined by the user. All the clocks on the network must have
the same Community name.
• Synchronisation failure: This setting is used to detect synchronisation discrepancies with
the master clock (type Sigma) or the time server (type Netsilon).
Multicast: Alarm triggered when the multicast synchronisation is absent for at least
1hour
Unicast: Alarm triggered when the unicast synchronisation is absent for 3 times the
duration of the poll (periodicity) and at least 1 hour (allowing for the NTP server
maintenance)
• Reboot: This setting is used to detect a clock reboot.
• Temperature: This setting is used to warn that the temperature range has been exceeded
(variable temperature range).
• Manipulation: This setting is used to trigger an alert if a setting is changed manually on the
clock (using the "S" and "+" keys).
All manuals and user guides at all-guides.com
EN
15