1. Safety and EMC Instructions
Please read carefully the following user manual and the
safety instructions before installing or operating the unit!
1.1 Installation
★ See installation instructions before connecting to mains power.
★ Condensation may occur if the UPS is moving directly from a cold
to a warm environment. The UPS must be absolutely dry before
being installation. It is recommended to have an acclimatization
time at least two hours.
★ Do not install the UPS near water or in damp environment.
★ Do not install the UPS where it would be exposed to direct sunlight
or near heat.
★ Do not connect appliances or items of equipment which would
overload the UPS (e.g. laser printers, etc.) to the UPS output.
★ Place cables properly to avoid someone treaded or tripped over
them.
★ Assure to connect with the earth reliably.
★ Connect the UPS only to a socket outlet which is earthed
shockproof type.
★ The building wiring socket outlet (shockproof socket outlet) must
be easily accessible to close to the UPS.
★ With the installation of the equipment, the sum of the leakage
current of the UPS and the connected load does not exceed
3.5mA.
★ An additional circuit breaker or fuse with rating 16A and breaking
capacity 3kA shall be used between power source and input when
installation this unit.
★ Do not block ventilation openings on the UPS's housing. Ensure
the air vents on the front, side and rear of the UPS are not blocked.