Press "Enter" button to confirm the output volt what you want.
■ Figure 7.1 Setting by LCD
To exit the setting mode that requests a pressing once on the "Enter" button;
to continue setting, press "Select" button. If no any pressing on the "Select"
or "Enter" button lasting for more than 10 seconds, the setting mode will exit
automatically.
The output frequency string "OPF", Bypass status string " bYPA", operating
mode string "MOdE", External Battery Ah string "EbAH", battery remaining
time string "bATT" , Charger current
string"CHG" would be presented
circularly. The only one voltage value can be selected in "220V", "230V",
"240V" at any time; The only one frequency value can be selected in "50Hz",
"60Hz" at any time; Bypass status can be selected in "000" or "001"(Here
000 means Bypass Disable,001 means Bypass Enable),The UPS would
turn to bypass mode in several seconds if "Bypass Enable" is selected, and
turn to no output mode in several seconds if "Bypass Disable" is selected;
Operating mode can be selected in "UPS", "ECO", "CVF"(Here "UPS"
means the normal online mode, "ECO" means the high efficiency mode, and
"CVF" means the converter mode), The mode change would be active only
after the UPS is turned on; External Battery Ah could be selected from "005"
to "300"(Here "005" means 5Ah total external battery); Charger Current
could be selected 3.0/6.0 for 1KL T and 1.5/3.0/4.5/6.0 for 2KL/3KL T
(Here 3.0 means 3A charger). The battery remaining time function could be
selected in "000" or "001". (Here 000 means battery remaining time function
is disabled, then the battery remaining time could not display on LCD in
-24-