LCD display in different mode
The different message/string would be displayed on the LCD screen
corresponding to their operating modes, and they are illustrated as the
following table. At any time, only one normal operating string or fault string
is presented, but the warning, if several warning happen at the same time,
they can be displayed on the LCD alternately. And the normal operating
mode string and the warning string would be shown circularly. Once one
fault is come forth, all previous warnings and the fault string would be shown
circularly.
Normal operating mode
No output mode
Bypass mode
Line mode
Battery mode
Battery test mode
ECO mode
Converter mode
It indicates the UPS is in Fault mode or
has some warnings.
Code
STbY
bYPA
LINE
bATT
TEST
ECO
CVCF
-12-