PowerWalker VFI 1000 TG Mode D'emploi page 32

Masquer les pouces Voir aussi pour VFI 1000 TG:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

bLOW
Battery low
bOPN
Battery open
CHGF
Charge fail
dCHF
Digital bigger
charger fail
bUSH
Bus high
bUSL
Bus low
bSFT
Bus soft start fail
bUSS
Bus short
TEPH
Inverter
temperature high
ITPH
Inner Ambient
temperature high
INVH
Inverter high
INVL
Inverter low
ISFT
Inverter soft start
fail
NTCO
Inverter NTC
open
Battery voltage is
low
Battery pack is not
connected
correctly
The charge is
broken
The charge is
broken
UPS internal fault
UPS internal fault
UPS internal fault
UPS internal fault
Inside
temperature of the
UPS is too high
The ambient
temperature is too
high
UPS internal fault
UPS internal fault
UPS internal fault
UPS internal fault
-29-
and after the battery
voltage is normal and
the mains is normal,
the UPS would Switch
to line mode
automatically again.
When audible alarm
sounding every
second, battery is
almost empty.
Do the battery test to
confirm.
Check the battery bank
is connected to the
UPS.
Check the battery
breaker is turn on.
Notify dealer.
Notify dealer.
Notify dealer
Notify dealer
Notify dealer
Notify dealer
Check the ventilation
of the UPS, check the
ambient temperature.
Check the environment
ventilation.
Notify dealer
Notify dealer
Notify dealer
Notify dealer