For 3000 TGS, Connect the output and ground wires to the terminal
block according to the table 5.1
Terminal
position
L
N
(3) Battery Input Connection for long backup time model
When connecting the external batteries it's recommended to pay
attention to these following items:
Use the battery pack with voltage:
24VDC for 1000 TG(S) (2 pcs of 12V batteries),
48VDC for 2000 TG(S) (4 pcs of 12V batteries),
72VDC for 3000 TG(S) (6 pcs of 12V batteries)
Note: Connection of batteries more than or less than required will
cause abnormality or permanent damage.
2*Schuko
4*Schuko
2*Schuko+1*C13
4*Schuko
2*Schuko+1*C19
Table 5.1
Wire function
Line In
Neutral In
Output Ground
-14-
4*C13+1*C19
3*C13+Terminal
Terminal wire size
rating
2
2
1.5mm
-2.5mm
(14AWG-12AWG )
3*C13
4*C13
6*C13
block
Tightening
torque
0.5Nm(4.4
Lb In)