Note: The default setting for bypass mode is no output after UPS
is connecting mains power and breaker is turned on. This can be
configurable.

5.5 Test function:

Test function is checking battery performance of the UPS system by
pressing the On-Switch for more than 1 second while UPS is operating
in Line mode, the UPS would detect whether the battery is connected
or the battery is weak. And the UPS could also implement this test
automatically and periodically, the period time is configurable.
5.6 Turn off the UPS:
(1) In Line Mode:
Press OFF button continuously for more than 1 second to turn off
the UPS, the UPS will get into no output or bypass mode. In
circumstance, the UPS might have output power if bypass mode is
enabled. Disconnect the mains power to turn off the output.
(2) In Battery Mode:
Press OFF button continuously for more than 1 second to turn off
the UPS, the UPS will get into no output or standby mode. After 10s
UPS will be shut down completely.
5.7 Audible alarm mute function:
If the audio alarm is too annoying in battery mode, the audio alarm is
able to mute by press ON button continuously for more than 1 second.
Moreover, the audio alarm will be active again when the battery
reaches low status for reminding that UPS output power will shut down
soon.
If the audio alarm is too annoying in bypass mode, the audio alarm is
able to mute by press OFF button continuously for more than 1 second.
This action doesn't affect the warning and fault alarm.
In any mode, if the warning or fault alarm is too annoying, you can mute
it by press ON button less than 0.5 second, and enable it by press ON
-17-