Electrical Connection - Terminals For Cable Bushing (Topcontrol Type 8630); Connection Pcb Of The Topcontrol Continuous With Screw Terminals And Jumpers; Terminal Configuration With Cable Bushings; Electrical Connection - Terminals For Cable Bushing - Burkert 2702 Manuel D'utilisation

Soupape de réglage à tête inclinée commandée par piston
Masquer les pouces Voir aussi pour 2702:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

electrical connection - terminals for cable bushinG

(topCONTROL type 8630)

attention!
For connection to the technical earth (ground) (TE), a threaded stud with nut is provided
on the connection module. To assure electromagnetic compatibility (EMC), connect this
stud to a suitable earthing (grounding) point using as short a cable as possible
(max. 30 cm).
note
Use of the 4 - 20 mA setpoint input
If the voltage supply of a TOPControl Continuous device fails in a row of such devices connec-
ted in series, the input of the failed device will become high-impedance. This will cause the 4
- 20 mA standard signal to fail. If this occurs, please contact Bürkert Service directly.
connection pcb of the topControl continuous with screw terminals and
jumpers

terminal configuration with cable bushings

terminal
allocation
1
Setpoint +
2
Setpoint GND
3
Analog position feedback +
4
Analog position feedback GND
5
Operating voltage +
6
Operating voltage GND
Remove the cover with the cable bushings to gain access
to the screw terminals. This is done by unscrewing the
4 self-tapping screws.
external connection
1
+ (0/4 ... 20 mA or 0 ... 5/10 V)
2
GND
3
+ (0/4 ... 20 mA or 0 ... 5/10 V)
completely isolated electrically
4
GND
5
24 V DC ± 10 %
max. residual ripple 10 %
6
C
ommissioninG
2702 - 21

Publicité

Table des Matières
loading

Table des Matières