Installation
Adjust minimum diameter of the electrical pipes to
accommodate the motor output and pipe length.
Do not bend or squash the pipes.
If hazardous situations can occur, provide an emergency off
switch according to DIN EN 809. The builder/operator must
make a decision according to this standard.
5.4.1
Counter swim unit electrical connection
The circuit is wired ready for connection. The connections
are carried out in accordance with the wiring diagram.
Connect the pneumatic hoses of the pneumatic buttons with
the control box.
The control box may only be mounted to the existing holes.
Connection onsite:
Ground fault circuit interrupter I
Fuse 1-phase 230 V/3-phase 400 V safety fuse 16 A slow or
16 A circuit breaker.
Short circuit breaking capacity I
All-pole emergency off switch with 0 and 1 labelling.
A connection has to be provided for equipotential bonding,
that is connected with the earthing strap.
Further information is provided in the connection diagram. The
above-mentioned parts are not included in delivery and must be
provided on site for the installation of the unit.
32 EN
≤ 30 mA
FN
≤ 6 kA
CN
06|2020