Siemens SITRANS TF2 Instructions De Service page 39

Transmetteur de température pour montage sur site avec lcd et pt100/

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Operating instructions
Function
Mode
Measured
(1)
Modify mea-
value
sured value
display
Password
2
higher
Unit of
4
change
measure
Start of
5
higher
"scaling"
measure-
ment
End of
6
higher
"scaling"
measure-
ment
Top limit
7
higher
value
violation
Bottom limit
8
higher
value
violation
Table 1
Parameter setting
SITRANS TF2
A5E00263328-02
Key function
M
⇒ M2 Measured value in mA or % or in
Modify decimal
position
physical unit
lower
"99"
Enter password
⇒ M4
"99" – Parameters
⇒ M5 Technical temperature units of
measure °C, °F, °R or K
The parameters 5, 6, 7, 8 and 9
are automatically converted to the
new unit
Factory setting °C
⇒ M6 Start of measurement in the
lower
selected unit of measurement
(Value entry between
–50 °C and 200 °C; note unit
selected)
Factory setting 0 °C
⇒ M7 End of measurement in the
lower
selected unit of measurement
(Value entry between
–50 °C and 200 °C; note unit
selected. The difference between
the measuring end and the mea-
suring start ≥10 K.)
Factory setting 100 °C
⇒ M8 ↑, violation limit for limit value set
lower
(Value entry between
–55 °C and 210 °C; note unit
selected)
Factory setting 100 °C
⇒ M9 ↓ , downward violation limit for
lower
limit value set (default 0.00 °C)
(Value entry between
–55 °C and 210 °C; note unit
selected)
Factory setting 0 °C
Technical description
Display,
explanatory comments:
39