Electrical Circuit Diagrams - Burkert 3003 Manuel D'utilisation

Actionneurs électriques ouvert/fermé
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

TechnicalData
6.4.3. electrical circuit diagrams
3-Point mode
N
-
TP/PE
1
Fig. 2:
Open/Closed Version
If voltage is applied simultaneously to terminals 2 and 3, terminal 2 is the leading one and the actuator moves to the OPEN position.
note!
Make certain in 3-point mode that the pulse duration of a controller lasts for at least 1 second. A pause time of at least 500 ms is required
before controller activation is repeated. Observe the duty cycle specified on the type label!
Please note the circuit board must remain power supplied to allow heating resistances working.
Type 3003
On-Off-Mode
Ph
N
+
-
Open Close
TP/PE
2
1
2
3
3
Ph
4 5
+
Open Close
symbol
FCO
FCF
FC1
FC2
Feedback
6 7
8 9
description
Limit switch ON
Limit switch OFF
Additional limit switch 1
Additional limit switch 2
english
11

Publicité

Table des Matières
loading

Table des Matières