Circuit Board For Actuator With Standard Signal Input - Burkert 3003 Manuel D'utilisation

Actionneurs électriques ouvert/fermé
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.4.
circuit board for actuator with
standard signal input
N
L
G
H
B
C
A
M
Fig. 6:
Circuit board
A
Electrical power supply
24 V AC/DC
B
Connection terminals of
the input signal
C Connection terminals of
the feedback
Type 3003
Installation
D
E
F
J
K
I
H
K2 plug-in jumper
I
K3 plug-in jumper
J
Green and red LED
D MEM pushbutton
E
CLOSE pushbutton
F
OPEN pushbutton
G K1 plug-in jumper
To prevent electromagnetic interference, shielded cables
must be used.
procedure:
Loosen the cable gland and feed the cable through.
Wire the signal transducer between terminals 15 and 16. Terminal
15 is the negative pole (-) and terminal 16 the positive pole (+).
Wire the position feedback sensor between terminals 13 and 14.
Terminal 13 is the positive pole (+) and terminal 14 the negative
pole (-).
Re-attach the cable gland.
If the connection voltage is 100 V to 240 V, a fuse must be
provided in the power supply.
english
K
LED yellow: Indicates the
power supply
L
Potentiometer
M
Motor connection
N
Heat resistor connection