Lift the cover off.
Wire the connections of the additional limit switches (FC1 and FC2)
according to the circuit diagram figures (see "Fig. 2" and "Fig. 3" ).
Tighten the cable gland after connecting the terminals.
Set the cover in place and screw it tight.
Reinstall the position indicator.
Only use 4 or 6 conductor cable with a diameter of 7 ... 12
mm for the ISO20 cable fitting.
Ensure that the cable in the ISO20 cable fitting is com-
pletely sealed when tightening the union nut.
7.3.1. setting the limit switches
The rotary actuator is supplied with the following factory
settings:
• The CLOSED limit switches are activated with the cams 2
and 4 (closed position).
• The OPEN limit switches are preset at a 90° rotation
angle.
The procedure for setting the limit switches is shown in "Fig. 4" and
"Fig. 5" .
14
english
Type 3003
Installation
Shaft
Motor
Body
Wrench (00679946)
Fig. 4:
Setting the limit switches. Limit switches max. 250 V / 5 A
Cams
Wrench
Adjustment
direction
Fig. 5:
Setting limit switches in counter clockwise and clockwise
directions
Electronic card
clOsed
Cam No. 4
Additional limit
black
switch CLOSED
Cam No. 3
Open
Additional limit
white
switch OPEN
Cam No. 2
clOsed
Motor limit switch
black
CLOSED
Open
Cam No. 1
Motor limit switch
white
OPEN
Setting in
clockwise direction
or setting in
counter clockwise
direction