Burkert 3003 Manuel D'utilisation page 17

Actionneurs électriques ouvert/fermé
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

control signal when current 0 – 20 ma
Press <MEM> and <OPEN> push-
button and switch on the card (hold
down pushbutton).
The RED LED lights up 3x.
R
Release <MEM> and <OPEN> push-
button and disconnect the card from
the power supply.
control signal when current 4 – 20 ma (preset)
Press <MEM> and <CLOSE> push-
button and switch on the card (hold
down pushbutton).
The RED LED lights up 3x.
R
Release <MEM> and <CLOSE>
pushbutton and disconnect the card
from the power supply.
Type 3003
Installation
learning mode
specify end positions
Press <OPEN> and <CLOSE>
pushbutton and switch on the card
(hold down pushbutton).
The RED and the GREEN LEDs light up.
G
R
Release <OPEN> and <CLOSE>
pushbutton.
Both LEDs go out.
Learning mode is selected.
Press <CLOSE> pushbutton to move
the shut-off valve into the closed
R
position.
The RED LED lights up.
Press <MEM> and <CLOSE> push-
button to save the closed position.
R
The RED LED lights up 2x.
Press <OPEN> pushbutton to move
the shut-off valve into the open
G
position.
The GREEN LED lights up.
Press <MEM> and <OPEN> push-
button to save the open position.
R
The GREEN LED lights up 2x.
english
17

Publicité

Table des Matières
loading

Table des Matières