Section 2
Additional Checks for QuietQube Models
Is the line set length, rise and drop within the
guidelines?
Are the suction and liquid line shut-off valves open?
Is the line set routed properly?
Are both refrigeration lines to remote condensing
unit run so they do not lay in water and are properly
insulated?
Does the condenser fan motor(s) operate properly after
start-up?
Have all the refrigeration fittings and joints been leak
checked?
Part Number 000007644 Rev 01 12/16
Has the condenser/condensing unit been installed to
prevent any roofing damage?
Have the refrigeration lines been insulated and secured
properly to prevent vibration?
Has the RCU remote condensing unit been located
where ambient temperatures will remain in the range
of -20° to 120°F (-29° to 48.9°C)?
Is a refrigeration oil trap (S-trap) installed if the
condenser is installed 21 to 35 feet (6 to 11 m) above
the ice machine head?
Installation Instructions
21