Section 2
C. SUCTION LINE OIL TRAPS
,
Do not form unwanted traps in refrigeration lines. Never
coil excess refrigeration tubing.
0 to 20 feet (0 to 6.1 m) Rise: No oil trap is required when
the condensing unit is located 20 feet (6.1 m) or less above
the ice machine head section.
21 to 35 feet (6.4 to 10.7 m) Rise: The suction line requires
an additional Oil Trap ("S" type) to be installed. Install
the trap as close as possible to midpoint between the
ice machine head section and remote condensing unit.
S-Trap Kits are available from Manitowoc.
Part Number 000007644 Rev 01 12/16
Caution
21 ft. (6.4 m)
OR MORE RISE
ADDITIONAL
TRAP KIT
REQUIRED
Service Loop
A service loop in the line set permits easy access to the ice
machine for cleaning and service.
A service loop is not considered an oil trap.
The service loop is not included when calculating
length, rise or drop of the tubing run.
Do not use hard rigid copper for the service loop.
,
If a line set has a rise followed by a drop, another
rise cannot be made. Likewise, if a line set has a drop
followed by a rise, another drop cannot be made.
Step 3
Lengthening or Reducing Line Set Lengths
,
Do not form unwanted traps in refrigeration lines. Never
coil excess refrigeration tubing.
When the line set requires shortening or lengthening, do
so before connecting the line set to the ice machine head
section or the remote condensing unit.
Installation Instructions
Caution
Caution
17