Types 2030, 2031, 2031 K, 2032,
Malfunctions
12.
MalfuncTiOns
Malfunction
Actuator does
Control connection interchanged *
not switch
→
CFA
→
CFB
→
CFI
* see Fig. 29:Pneumatic Connection in the chapter of
the same name.
Control pressure too low
→
See pressure specifications on the rating
plate.
Medium pressure too high
→
See pressure specifications on the rating
plate.
Valve is not
Medium pressure too high
→
sealed
See pressure specifications on the rating
plate.
Control pressure too low
→
See pressure specifications on the rating
plate.
Flow rate
PTFE diaphragm bulging
→
reduced
Replace diaphragm.
2033, 2037
Cause / remedial action
Connect lower control connection
Connect upper control connection
Upper control connection: Close
Lower control connection: Open
13.
spare parTs
Warning!
risk of injury when opening the actuator housing!
The actuator contains a tensioned spring. If the housing is opened,
there is a risk of injury from the spring jumping out!
•
Carefully open the actuator housing and hold it in such a way
that any parts which jump out cannot injure anyone or damage
anything.
CauTion!
risk of injury and/or damage by the use of incorrect parts!
Incorrect accessories and unsuitable spare parts may cause injuries
and damage the device and the surrounding area.
•
Use only original accessories and original spare parts from
Bürkert.
Types 2030, 2031, 2031 K, 2032 and 2033 are available as spare
parts for the piston-controlled diaphragm valves.
•
Seal set,
•
Diaphragm.
English