5 Mounting
Structural Stability:
☐ When mounting with feet or profile rails, the width of one foot or the profile rail must be at
least 175 mm (7 in) to ensure structural stability.
☐ The inverter must be attached under the following conditions:
– Inclination of the support surface: > 3°
– Wind speed (without wind gusts): > 25 m/s (82 ft/s)
– Height of the feet or the profile rail: > 100 mm (4 in)
☐ When mounting with profile rails, an attachment or fixation by loading is required. When
mounting with profile rails, SMA Solar Technology AG recommends to bolt the profile rails
e.g. to the profile of the module frame or to attach a sheet metal (which can be weighted with
stones or with sandbags) at the profile rails. This will ensure that the inverter is fixed.
_
+
_
+
Figure 5 : Attachment of the inverters (examples)
Recommended Clearances:
To guarantee optimal operation and adequate heat dissipation for the inverter, the following
requirements for clearances should be observed. This will prevent the inverter power output from
being reduced due to excessive temperatures. However, smaller clearances are permitted without
causing any risk.
24
STP33-62-US-41-IA-xx-13
SMA Solar Technology AG