Technical data

2.1

General data and operating conditions

General data
Conformity and approval
Conformity
CE
Approval
UL
Protection of persons and devices
Type of protection
Earth leakage current
Insulation of control
circuits
Insulation resistance
Protective measures
EMC
Noise emission
Noise immunity
EDKVS9332X DE/EN/FR 2.0
General data and operating conditions
73/23/EEC
Low-Voltage Directive
UL 508C
Power Conversion Equipment
for USA and Canada
1D74, file No. E132659
EN 60529
IP20
IP41 on the heatsink side for thermally separated mounting
(push-through technique).
NEMA 250
Protection against contact in accordance with type 1
EN 61800-5-1
> 3.5 mA
EN 61800-5-1
Safe mains isolation by double (reinforced) insulation for
terminals X1 and X5.
Basic insulation (single isolating distance) for terminals X3,
X4, X6, X7, X8, X9, X10 and X11.
EN 61800-5-1
Site altitude < 2000 m: Overvoltage category III
Site altitude > 2000 m: Overvoltage category II
http://www.DataSheet4U.net/
Against short circuit, earth fault (earth-fault protected during
mains connection, limited earth-fault protection during
operation), overvoltage, motor overtemperature (input for
PTC or thermal contact)
EN 61800-3
Cable-guided, up to 10 m motor cable length with mains
filter A: category C2.
Radiation, with mains filter A and installation in control
cabinet: category C2
EN 61800-3
Category C3
Technical data
Regulations and safety
instructions must be observed!
2