Electrical installation
Basic devices in the power range 15 ... 30 kW

Motor connection

4.4.3
Motor connection
Note!
ƒ
ƒ
Shield sheet installation
Stop!
Do not use lugs as strain relief.
T1
T2
Fig.4-10
152
Fusing the motor cable is not required.
The drive controller features 2 connections for motor temperature
monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal contact
(NC contact).
– Pins X8/5 and X8/8 of the incremental encoder input (X8) for connecting a
KTY thermal sensor.
PE
U
V
3.4 Nm
a
a
30 lb-in
0
Installation of shield sheet for drive controllers 15 ... 30 kW
Fasten the shield sheet with two self-tapping screws ∅ 4 × 14 mm (a)
W
h t t p : / / w w w . D a t a S h e e t 4 U . n e t /
9300vec131
EDKVS9332X DE/EN/FR 2.0