Fuses and cable cross-sections for the mains supply
9300
Type
EVS9321-xx
EVS9322-xx
EVS9323-xx
EVS9324-xx
EVS9325-xx
EVS9326-xx
9300
Type
EVS9321-xx
EVS9322-xx
EVS9323-xx
EVS9324-xx
EVS9325-xx
EVS9326-xx
Fuse (fuses of utilisation category gG/gL or semiconductor fuses of utilisation category gRL)
Circuit breaker
Fuse
1)
The specifications are recommendations. Other designs/laying systems are possible (e.g. to VDE 0298-4). The cable
cross-sections apply under the following conditions: Use of PVC-insulated copper leads, conductor temperature
< 70 °C, ambient temperature < 40 °C, no bundling of cables or cores, three loaded cores.
The max. connection cross-section of the terminal strip is 4 mm
2)
Universal current sensitive earth-leakage circuit breaker
3)
Use only UL-approved cables, fuses and fuse holders. UL fuse: voltage 500 ... 600 V, tripping characteristic "H", "K5"
or "CC".
4)
For short-time mains interruptions, use circuit breakers with tripping characteristic "C"
National and regional regulations must be observed
EDKVS9332X DE/EN/FR 2.0
Basic devices in the power range 0.37 ... 11 kW
Mains
[U
]
r
3/PE AC
320 ... 528 V
45 ... 65 Hz
Mains
Mains choke
[U
]
Type
r
ELN3-0700H003
ELN3-0700H003
3/PE AC
320 ... 528 V
ELN3-0450H004
45 ... 65 Hz
ELN3-0250H007
ELN3-0160H012
ELN3-0120H025
Electrical installation
Mains connection, DC supply
Operation without mains choke or mains filter
Installation
according to
1)
EN 60204-1
L1, L2, L3, PE
Laying system
B2
C
2
2
[A]
[A]
[mm
]
[mm
4)
6
C6
1
1
B6
4)
6
C6
1
1
B6
10
B10
1.5
1
Operation only allowed with mains choke or mains filter
25
B20
6
4
Operation only allowed with mains choke or mains filter
Operation with mains choke or mains filter
Installation
according to
1)
EN 60204-1
L1, L2, L3, PE
Laying system
B2
C
2
2
[A]
[A]
[mm
]
[mm
http://www.DataSheet4U.net/
4)
6
C6
1
1
B6
4)
6
C6
1
1
B6
10
B10
1
1
10
B10
1.5
1
20
B20
4
4
35
B32
–
6
2
, with pin-end connector 6 mm
2)
FI
Installation according
3)
to UL
L1, L2, L3, PE
]
[A]
[AWG]
[mA]
5
18
5
18
300
10
16
25
10
300
2)
FI
Installation according
3)
to UL
L1, L2, L3, PE
]
[A]
[AWG]
[mA]
5
18
5
18
300
5
18
10
16
20
12
25
10
2
141
4
datasheet pdf - http://www.DataSheet4U.net/